PNOZ X7P
Operating Manual PNOZ X7P
21027-EN-05
16
Conventional thermal
current while loading
several contacts
777053
777056
777059
Ith per contact at UB AC;
AC1: 240 V, DC1: 24 V
Conv. therm. current
with 1 contact
4 A
4 A
–
Conv. therm. current
with 2 contacts
3 A
3 A
–
Times
777053
777056
777059
Switch-on delay
With automatic start
typ.
230 ms
230 ms
50 ms
With automatic start
max.
700 ms
700 ms
150 ms
With automatic start
after power on typ.
230 ms
230 ms
50 ms
With automatic start
after power on max.
700 ms
700 ms
150 ms
With manual start typ.
140 ms
140 ms
35 ms
With manual start max.
700 ms
700 ms
150 ms
Delay-on de-energisation
With E-STOP typ.
70 ms
70 ms
45 ms
With E-STOP max.
100 ms
100 ms
70 ms
With power failure typ.
70 ms
70 ms
45 ms
With power failure max.
100 ms
100 ms
70 ms
Recovery time at max.
switching frequency 1/s
After E-STOP
120 ms
120 ms
50 ms
After power failure
120 ms
120 ms
150 ms
Supply interruption before
de-energisation
20 ms
20 ms
20 ms
Environmental data
777053
777056
777059
Climatic suitability
EN 60068-2-78
EN 60068-2-78
EN 60068-2-78
Ambient temperature
Temperature range
-10 - 55 °C
-10 - 55 °C
-10 - 55 °C
Storage temperature
Temperature range
-40 - 85 °C
-40 - 85 °C
-40 - 85 °C
Climatic suitability
Humidity
93 % r. h. at 40 °C
93 % r. h. at 40 °C
93 % r. h. at 40 °C
Condensation during op-
eration
Not permitted
Not permitted
Not permitted
EMC
EN 60947-5-1, EN
61000-6-2, EN 61326-3-1
EN 60947-5-1, EN
61000-6-2, EN 61326-3-1
EN 60947-5-1, EN
61000-6-2, EN 61326-3-1