7-7
Operating Manual: PMImicro diag
Location description
The location description is a precise description of the position of the
device with the stated equipment identifier and displayed parameters.
When performing diagnostics on the PNOZmulti, the location description is
displayed in addition to a description of the event/action, provided the user
has entered this information. The user himself creates the location
description.
INFORMATION
The location description can only be configured on the PNOZmulti.
Event list
The event list is shown on the PMImicro diag, which receives the event
telegrams from the PSS. For each event, a check is made to examine
whether the event message corresponding to the event has to be
displayed and entered in the event list (intelligent evaluation). For example,
if it concerns an event that has occurred as a consequence of a previous
event, the event will be ignored.
A check is also made to see whether the user requires further information
on an event. For example, if the PSS registers that an I/O-Group on
SafetyBUS p has stopped, the display unit calls up the error stack of the
device that triggered the stop, displays the relevant event messages and
enters them in the event list.
The event messages are deleted from the event list as soon as the cause
of the error has been rectified (see page 7-11).
INFORMATION
The PMImicro diag displays a maximum of 10 event messages. When an
event message is deleted, subsequent event messages move up
automatically.