
Commissioning
Operating Manual PMCprotego S12(C)
1002528EN03
79
8.
Press the lefthand operator key
for at least 2 seconds.
– The configuration file default.pdis starts downloading to the safety card. Display:
"…".
– Once the configuration file has been downloaded, the safety card starts up. The
safety card is in "STARTUP" condition ("RUN" LED flashes).
– If the download has been successful, the safety card switches to "RUN" condition
("RUN" LED is lit).
7.4
Safety checks
The machine manufacturer must check and verify the functionality of the employed safety
functions.
}
The safety functions may only be checked by qualified personnel.
The safety function must be checked
}
After initial commissioning
}
After changing the configuration of the safety functions
}
After exchanging the safety card or servo amplifier
A full check comprises
}
Proper execution of the employed safety functions
}
Inspection of the parameters
The result of the check on each safety function must be documented in a test report. This
test report must be signed.
INFORMATION
If any of the parameters for the safety functions have been changed, the
check must be repeated and this must be recorded in the test report.
Regular checks
Check the safety functions at regular intervals. The aim of these regular checks is to un
cover any changes to the plant/machine, safety functions and ambient conditions.
You must comply with the requirements of the applicable national regulations.
The intervals you select will depend on the application, the overall system and the associ
ated risk analysis. The test interval should not exceed one year.
Brake test
Depending on the application, the regular checks may include a test of the internal (motor
brake) and external brake.
INFORMATION
Please refer to "Safe brake test SBT" for details of the function of the safe
brake test.