Connect the TP 6…PS to a 24 V DC power supply.
NOTE:
To ensure safe operation, use safety extra-low voltage (SELV) according to DIN
EN 61131 as a supply voltage.
This device is protection class I item of equipment.
3.2.2
Grounding
This is part of the power connector.
3.2.3
Ferrite core
NOTE:
A ferrite core is required for initial version of hardware, indicated on the product label
as VC00. Starting with VC01, the ferrite core is built into the internal power supply.
A ferrite core is included with the TP 6…PS units. It is required to reduce EMI interference
when the device is installed within the EEC.
Figure 3
-
6
Ferrite core
1. Connect the appropriate conductors to the supplied power connector.
2. Open the core.
3. Lay the three conductors in the core and wrap them around the outside so a second
strand is routed through the core. There must be between 3 and 5 cm of conductor be
-
tween the core and connector.
4. Snap the core closed, taking care to not pinch the conductors.