Installation
4109_en_B
PHOENIX CONTACT
13/28
3.2.4
Serial communication
The configurable D-SUB 9 port is a future enhancement. It is included in the document
for future reference when the capability is released.
The D-SUB 9 port can be configured to support RS-422, RS-485, or 5-wire RS-232 physical
layer signal levels. The serial port is configured in the Visu+ configuration environment as
either
When in Visu+ (Express), the user will select the communication driver (RealTimeDB), and
then configure the port within the station properties.
The function of the pins in the D-SUB 9 connector varies with the different configuration
settings.
Port 1
RS-232
Port 2
RS-422/485
Table 3
-
2
D-SUB 9 pinout
D-SUB 9 pin
Function
1
TX+
RS-485 transmitted data plus
2
TXD
RS-232 transmitted data
3
RXD
RS-232 received data
4
RX+
RS-485 received data plus
5
GND
Ground
6
–
Not used
7
–
Not used
8
TX-
RS-485 transmitted data minus
9
RX-
RS-485 received data minus