AXC F 1050
PHOENIX CONTACT
107709_en_00
3.5
Diagnostics and status indicators
The diagnostics and status indicators are used for quick local error diagnostics.
Figure 3-7
Diagnostics and status indicators
X4
U
L
U
L
E
TH
PWR
PN/
A
XC/P
L
C
BF-C
BF-D
SF
BF-D
SF
BF-C
D
E
Table 3-1
Controller diagnostics and status indicators
Desig-
nation
Color
Meaning
Status
Description
PN: PROFINET controller/device function
BF-C
Red
PROFINET con-
troller:
Communication
error (bus fault)
AXC F 1050 as a PROFINET controller
Off
–
The AXC F 1050 has established an active communication
connection to each configured PROFINET device.
Or:
–
The PROFINET controller function is switched off.
On
No link status on the Ethernet interfaces and/or no 100 Mbit
transmission and/or no full duplex mode.
Flashing
(1 Hz)
Link status present, at least one configured PROFINET device
does not have a communication connection.
BF-D
Red
PROFINET
device:
Communication
error (bus fault)
AXC F 1050 as a PROFINET device
Off
–
A PROFINET controller has established an active commu-
nication connection to the AXC F 1050 (PROFINET de-
vice)
Or:
–
The PROFINET device function is switched off.
On
No PROFINET communication (no link status at the Ethernet in-
terfaces).
Flashing
(1 Hz)
Link status present, no communication connection to the
PROFINET controller.
SF
Red
Group error
(PROFINET)
Off
PROFINET diagnostics not present.
On
PROFINET diagnostics present.