Transmission speed
100 Mbps
Number of local bus devices that can be connected
63, maximum
Axioline F local bus interface
NOTE: Electronics may be damaged when overloaded – observe the current consumption of the Axioline F modules.
Observe the current consumption of each device when configuring an Axioline F station. It is specified in every module-specific data sheet.
The current consumption can differ depending on the individual module. The permissible number of devices that can be connected therefore
depends on the specific station structure.
General supply
Use a
p
ower supply without fall-back characteristic curve (see Section “Sizing of the power supply” on page 43).
Controller supply
Supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, ripple included)
Power supply at U
Bus
2 A
Residual ripple
±5 %
Current consumption at nominal voltage
Typ. 408 mA (without I/Os and UL = 24 V)
Max. 976 mA (with 2 A at U
Bus
for the I/Os and U
L
= 24 V)
Power consumption at U
L
Typ. 9.8 W (without I/Os)
Max. 23.5 W (with 2 A load at U
Bus
for the I/Os)
Functional earth grounding
Logic GND and functional earth ground FE are permanently connected in the
housing.
Protective measures
Surge voltage
Polarity reversal
Input protective diode, pulse load up to 1500 W
Serial diode in the lead path of the power supply unit; in the event of an error
only a low current flows. In the event of an error, no fuse trips within the exter-
nal power supply unit.
NOTE: Electronics may be damaged when overloaded
Observe the current consumption of the Axioline F modules
Observe the current consumption of each device when configuring an Axioline F station. It is specified in every module-specific data sheet.
The current consumption can differ depending on the individual module. The permissible number of devices that can be connected therefore
depends on the specific station structure.
Protection by the external power supply unit
Ensure protection of 2 A through the external power supply unit.
Connection data
Designation
Axioline F supply plug
Connection method
Push-in technology
Conductor cross section, solid
0.2 mm
2
... 1.5 mm
2
Conductor cross section, stranded
0.2 mm
2
... 1.5 mm
2
Conductor cross section [AWG]
24 ... 16
Summary of Contents for AXC 3050
Page 1: ...User manual Installation and operation of the AXC 3050 controller UM EN AXC 3050...
Page 8: ...AXC 3050 8 PHOENIX CONTACT 8686_en_01...
Page 10: ...AXC 3050 10 PHOENIX CONTACT 8686_en_01...
Page 34: ...AXC 3050 34 PHOENIX CONTACT 8686_en_01...
Page 94: ...AXC 3050 94 PHOENIX CONTACT 8686_en_01...
Page 110: ...AXC 3050 110 PHOENIX CONTACT 8686_en_01...
Page 136: ...AXC 3050 136 PHOENIX CONTACT 8686_en_01...
Page 144: ...AXC 3050 144 PHOENIX CONTACT 8686_en_01 U Updating the firmware 133...