onlinecomponents.com
Appendix: Displaying the Figure Display
6170
B
39
9
Appendix: Displaying the Figure Display
In the basic state of the configuration mode, the display shows one after the other
the addresses of all detected slaves at a rate of two per second. A blank display
means that the
LDS
is empty, i.e. no slaves were detected.
In the basic state of the protected operating mode, the display is either blank or
displays the address of a faulty assignment (see chapter 5.3.2).
During manual address programming, the slave address display has a different
meaning (see chapter 5.4 and 5.5).
All displayed numbers that are bigger than 31 and therefore can not be interpreted
as a slave address are status or error messages of the master. They have the fol-
lowing meanings:
39 Advanced AS-i diagnostics: If a 39 appears on the display after
pressing the ’set’-button a short-time AS-i power failure occured.
OFP The AS-i master is in off-line phase.
SEA The AS-i master is in detection phase.
42 The AS-i master is in activation phase.
43 The AS-i master starts the normal operating mode.
70 Hardware error: The AS-i master’s EEPROM cannot be written to.
72 Hardware error: The PIC processor does not respond.
73 Hardware error: The PIC processor does not respond.
74 Checksum error in the EEPROM.
80 Error while attempting to exit the configuration mode: A slave with
address zero exists.
81 General error while changing a slave address.
88 Display test while starting up the AS-i master
90 Error while changing a slave address in protected operating mode:
No slave with address 0 existing.
91 Error while changing slave address: Target address is already occu-
pied.
92 Error while changing slave address: New address could not be set.
93 Error while changing slave address: New address could only be
stored volatile in the slave.
94 Error while changing slave address in protected operating mode:
Slave has wrong configuration data.
95 Error while changing slave address in protected operating mode:
The configuration error was caused by one slave too many (instead
of one missing slave).
Summary of Contents for 27 41 40 6
Page 2: ...o n l i n e c o m p o n e n t s c o m...
Page 4: ...o n l i n e c o m p o n e n t s c o m...
Page 6: ...o n l i n e c o m p o n e n t s c o m 6170B 4...
Page 10: ...o n l i n e c o m p o n e n t s c o m Table of Contents 6170B 4...
Page 12: ...o n l i n e c o m p o n e n t s c o m The Symbols Used 6170B 6...
Page 14: ...o n l i n e c o m p o n e n t s c o m Safety 6170B 8...
Page 16: ...o n l i n e c o m p o n e n t s c o m General Information 6170B 10...
Page 26: ...o n l i n e c o m p o n e n t s c o m Operating the AS i INTERBUS Gateway 6170B 20...
Page 42: ...o n l i n e c o m p o n e n t s c o m AS i INTERBUS Gateway 6170B 36...
Page 46: ...o n l i n e c o m p o n e n t s c o m Appendix Displaying the Figure Display 6170B 40...
Page 50: ...o n l i n e c o m p o n e n t s c o m Technical Data 6170B 44...