Operating the AS-i/INTERBUS Gateway
6170
B
16
In configuration mode, all recognized slaves are activated except of slave zero.
The AS-i master is in normal operation. There is data exchange between the AS-i
master and all AS-i slaves detected by the master regardless of whether the de-
tected AS-i slaves were projected before.
5.3
Protected Operating Mode
5.3.1
Switching to Protected Operating Mode
The configuration mode can be left by pressing the “MODE” button.
Pressing the button shortly:
Exits the configuration mode without projecting the current AS-i configuration.
Pressing the button for more than five seconds:
Exits the configuration mode and projects the actual AS-i configuration. Simul-
taneously the actual AS-i configuration is stored as nominal configuration in the
EEPROM.
In the protected operating mode, only AS-i slaves that are projected and whose
actual configurations match the nominal configurations will be activated.
5.3.2
Configuration Errors in Protected Operating Mode
As long as there is no configuration error, the numeric display is turned off while in
protected operating mode. Otherwise, the address with a faulty assignment is dis-
played. A faulty assignment occurs when a slave has been recognized or projec-
ted but cannot be activated.
If there are more than one faulty assignments the one that was first detected is dis-
played. Pressing the “SET” button shortly displays the next higher faulty address.
Shortly appearing configuration errors are stored in the device (advanced AS-i dia-
gnosis). The last error that occurred can be displayed by pressing the set button.
If a short AS-i power failure is responsible for the configuration error the display
shows a “39”.
When delivered the device is in configuration mode.
In contrast with the configuration mode in the protected mode there
is only data exchange between the AS-i master and the projected
AS-i slaves.
If the system detects an AS-i slave with address zero on the AS-i, it
can not leave the configuration mode.
Summary of Contents for 27 41 40 6
Page 2: ...o n l i n e c o m p o n e n t s c o m...
Page 4: ...o n l i n e c o m p o n e n t s c o m...
Page 6: ...o n l i n e c o m p o n e n t s c o m 6170B 4...
Page 10: ...o n l i n e c o m p o n e n t s c o m Table of Contents 6170B 4...
Page 12: ...o n l i n e c o m p o n e n t s c o m The Symbols Used 6170B 6...
Page 14: ...o n l i n e c o m p o n e n t s c o m Safety 6170B 8...
Page 16: ...o n l i n e c o m p o n e n t s c o m General Information 6170B 10...
Page 26: ...o n l i n e c o m p o n e n t s c o m Operating the AS i INTERBUS Gateway 6170B 20...
Page 42: ...o n l i n e c o m p o n e n t s c o m AS i INTERBUS Gateway 6170B 36...
Page 46: ...o n l i n e c o m p o n e n t s c o m Appendix Displaying the Figure Display 6170B 40...
Page 50: ...o n l i n e c o m p o n e n t s c o m Technical Data 6170B 44...