Operating the AS-i/INTERBUS Gateway
6170
B
18
5.5
Programming the Address in Case of Configuration Errors
5.5.1
Automatic Address Assignment
For automatic programming to work, some requirements must be met:
1.The AS-i master must be in the protected operating mode.
2.The “Auto_Address_Assign”
1
release flag must be set.
3.Only one of the projected slaves may not be detected.
If these requirements are met, the AS-i master’s “
PRG
” LED lights up and a slave
with address zero will be automatically assigned to the operating address of the
missing slave. The "Automatic Address Assignment" can be activated and deacti-
vated via the software "AS-i Control Tools". .
5.5.2
Manual Address Assignment
In protected operating mode, wrong assignments are displayed as errors (see
chapter 5.3). By pressing the “SET” button, you can display all faulty assignments
one after the other. By pressing the “SET” button for more than five seconds, you
can select the currently displayed address as a potential target address, and the
display starts to blink.
If the faulty slave was previously replaced by a slave with address zero, the new
slave can now be programmed for the blinking address by pressing the “SET” key
One of AS-i’s great advantages is the automatic address assign-
ment. If a slave fails, it can be replaced by one of the same type with
address zero. The master will detect the replacement and automati-
cally addresses the new slave with the address of the faulty one.
1. By deletion of flag "Auto_prog" the user can close "automatic addressing".
If the two slaves have different configuration data, i.e. are not of the
same type as far as AS-i is concerned, the automatic address
assignment will not be carried out.
Only slaves with address 0 can get a new address by the master.
If several slaves fail, they cannot be replaced automatically by the
AS-i master. Then these addresses have to be set manually. If this
should not be done via the host interface (using the AS-i Control
Tools) or with a hand held addressing device, the slave addresses
can also be changed with the help of the push buttons and the figure
display of the device.
Summary of Contents for 27 41 40 6
Page 2: ...o n l i n e c o m p o n e n t s c o m...
Page 4: ...o n l i n e c o m p o n e n t s c o m...
Page 6: ...o n l i n e c o m p o n e n t s c o m 6170B 4...
Page 10: ...o n l i n e c o m p o n e n t s c o m Table of Contents 6170B 4...
Page 12: ...o n l i n e c o m p o n e n t s c o m The Symbols Used 6170B 6...
Page 14: ...o n l i n e c o m p o n e n t s c o m Safety 6170B 8...
Page 16: ...o n l i n e c o m p o n e n t s c o m General Information 6170B 10...
Page 26: ...o n l i n e c o m p o n e n t s c o m Operating the AS i INTERBUS Gateway 6170B 20...
Page 42: ...o n l i n e c o m p o n e n t s c o m AS i INTERBUS Gateway 6170B 36...
Page 46: ...o n l i n e c o m p o n e n t s c o m Appendix Displaying the Figure Display 6170B 40...
Page 50: ...o n l i n e c o m p o n e n t s c o m Technical Data 6170B 44...