20 |
Page
V2.1
Routing Power Cables
Note:
Continuous metal conduit should be used for all power cables to reduce radiated
electromagnetic interference (EMI). The conduit must be securely grounded to the
converter enclosure and the motor case. Conduit hubs should be IMC or rigid steel conduit
and be UL listed. Conduit hub locations can be seen in
Route power cables through the supplied openings in the bottom of the enclosure, using
appropriate conduit or strain relief devices.
Important Note:
If new openings are cut, be sure to completely remove all resulting metal
shavings.
Figure 15
– PT Small Frame Conduit
Locations
Figure 16
– PT Medium Frame Conduit
Locations
Figure 17
– PT Large Frame Conduit Locations
Small Frame Models:
PT407, PT410, PT415,
PT420
Medium Frame Models:
PT007, PT010, PT020,
PT430
Large Frame Models:
PT030, PT040, PT050,
PT060, PT075, PT440,
PT450, PT460, PT475,
PT4100