28 |
Page
V2.1
Infinite Restarts
WARNING!
Risk of electric shock. De-energize the unit by disconnecting all incoming
sources of power, then wait 30 minutes for internal charges to dissipate before servicing
the equipment.
Infinite Restarts will allow the converter to restart an unlimited number of times after fault
conditions. This procedure will require wiring two ON/OFF switches to the converter.
Standard light switches will work. See
for wiring diagram. To add a startup delay,
follow the steps below:
Step
Action
1
Turn power to PT
OFF
2
Remove jumper wire between AUX1
and COM
3
Wire dry contact switch between AUX3
and COM (now called SW3)
4
Wire dry contact switch between AUX4
and COM (now called SW4)
5
Turn power to the PT
ON
6
Toggle
SW4
until you see INFINITE
RESTARTS on screen
7
Toggle
SW3
to select between YES or
NO
Wait several seconds until “
Programmed Successfully
” is shown on the display, and then
return switches to the
OFF
position. Turn power to converter
OFF
, re-install jumper wire
between
AUX1
and
COM
, then reapply power to converter.