Table 3
– 240 V PTE Models and Ratings
Model
Power
(HP)
Output
(kVA)
Max Steady
State Output
Current
(AAC)
Input
Voltage
Range
(VAC)
Max AC
Input
Current (A)
Standby
Power/Energy,
(W/BTU/hr)
Full Load
Energy
Loss
(BTU/hr)
PTE007
PTE007QT
7.5
10.8
26
187-260
45
70/239
479
PTE010
PTE010QT
10
14.9
36
62
74/252
661
PTE015
15
21.6
52
90
77/263
958
PTE020
20
26.6
64
111
80/273
1180
Table 4
– Voltage Doubling PTE Models and Ratings
Model
Power
(HP)
Output
(kVA)
Max Steady
State Output
Current (AAC)
Input
Voltage
Range
(VAC)
Max AC
Input
Current (A)
Standby
Power/Energy
(W/BTU/hr)
Full Load
Energy Loss
(BTU/hr)
PTE207
7.5
10.8
13
187-260
45
1938
PTE210
10
14.9
18
62
2685
PTE215
15
22.4
27
94
4029
PTE220
20
26.6
32
111
4777
Table 5
– 480 V PT Models and Ratings
Model
Power
(HP)
Output
(kVA)
Max Steady
State Output
Current (AAC)
Input
Voltage
Range
(VAC)
Max AC
Input
Current (A)
Standby
Power/Energy,
(W/BTU/hr)
Full Load
Energy
Loss
(BTU/hr)
PT407
7.5
10.8
13
440-520
22
52/177
479
PT410
10
14.9
18
32
68/232
661
PT415
15
22.4
27
47
71/242
994
PT420
20
26.6
32
55
74/252
1180
PT430
30
38.2
46
80
87/297
1694
PT440
40
50.7
61
105
180/614
2249
PT450
50
64
77
134
190/648
2839
PT460
60
75.6
91
157
220/751
3358
PT475
75
88.9
107
185
270/921
3992
PT4100
100
118
142
246
300/1024
5239
Summary of Contents for Phase Perfect PT007
Page 13: ...7 Page V2 1 Dimensional Drawings Figure 4 PT Small Frame Dimensions...
Page 14: ...8 Page V2 1 Figure 5 PT Medium Frame Dimensions...
Page 15: ...9 Page V2 1 Figure 6 PT Large Frame Dimensions...
Page 16: ...10 Page V2 1 Figure 7 PTE Frame 1...
Page 17: ...11 Page V2 1 Figure 8 PTE Frame 2...
Page 46: ...40 Page V2 1 NOTES...