Operation manual
12
5.3.2 Operation with the wireless remote control
Operation of the turnstile with the WRC is similar to that with the RC-panel.
The buttons on the WRC tag act the same way as those on the RC-panel.
The operation manual for the WRC is supplied within the delivery set of that item.
5.3.3 Operation with an ACS controller
At the pulse control mode control over the turnstile via an ACS controller is similar to that with the
RC-panel.
At the potential control mode control over the turnstile via an ACS controller is similar to that with
the RC-panel and lies in forming of a low-level signal on the contacts
Stop
,
Unlock
A
and
Unlock
B
relatively to the contact
GND
.
The difference in the operation logic at the potential control mode and at the pulse control mode
(the command on the closing of the passage is generated only at the moment of releasing the RC
button, corresponding to the passage direction A(B). Therefore, for arranging single passages at
the potential control mode it is recommended to remove the control low-level signal at the
beginning of the “
PASS
” signal for the corresponding direction.
The passage through the turnstile in the A (B) direction is registered by a status of the outputs
PASS
A
(
B
) and
Common
.
5.4 Additional devices connectable to the turnstile
The following additional devices can be connected to the turnstile:
•
Intrusion detector and siren;
•
Emergency unblocking device;
•
Remote indicators.
The intrusion detector is connected to the “XT2” connector block, and the siren is connected to the
“XT1.H” connector block of the CLB according to the connection layout (see Fig.
should be normally closed contacts on the intruder detector.
Note!
Only the manufacturer should carry out the installation of the intrusion detector on the
turnstile housing.
If the turnstile is blocked (“Always locked” mode or “Both directions closed” one, see Tables 2 and 3)
and a signal comes from the intrusion detector, the “Alarm” signal is generated. The “Alarm” signal is
disabled after 5 sec. or by performing of any received command. The signal from the intrusion
detector is ignored for the period of authorized unblocking of the turnstile (in either or both
directions). If within 3 sec after the
“Always locked”/“Both directions closed”
mode is set, the signal
from the intrusion detector comes, it is ignored. The intrusion detector status signal is constantly
transmitted to the “Det Out” and “Common” contacts of the CLB “XT1.H” connector block (see
Fig. 4).
The emergency unblocking device is connected to the “XT1.L” connector block of the CLB in
accordance with the connection layout (see Fig. 4 and 13). If the “Fire Alarm” input is not used, it is
necessary to set a jumper between contacts “Fire Alarm” and “GND”. This jumper is set at the
factory before the delivery.
Operation of the turnstile under commands of the emergency unblocking device:
At the pulse control mode and when a low-level signal is eliminated from the “Fire Alarm” input,
both passage directions become open for the whole period of the signal absence. Other
controlling commands are ignored at that. When the low-level signal appears at the “Fire Alarm”
input, the turnstile turns to the “Always locked” mode.
At the potential control mode and when a low-level signal is eliminated from the “Fire Alarm”
input, both directions become open for the whole period of the signal absence. Other controlling
commands are ignored at that. When the low-level signal appears at the “Fire Alarm” input, the
directions turn to the mode in accordance with the signal levels at the inputs “Unlock A”,
“Unlock B” and “Stop”.