AS-i/PROFIBUS Gateway
PROFIBUS DP
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Is
s
ue dat
e -
12.
8.
2007
51
9.1
DP Telegrams
9.1.1
Diagnosis
DP Diagnosis - Double Master
ec-flags (high):
Bit 0:periphery fault
Bit 1 … Bit 2reserved
Bit 3:failure redundant 24 V
Bit 4:earth fault
PDU byte
user byte
DP
DP V1
user
1
–
station_status 1
4
2
–
station_status 2
4
3
–
station_status 3
4
4
–
master address
4
5
–
ident high
4
6
–
ident low
4
7
1
header
4
4
8
2
type
4
9
3
slot
4
10
4
spec
4
11
5
ec-flags (high), circuit 1
4
12
6
ec-flags (low), circuit 1
4
13
7
delta (0…7), circuit 1
4
14
8
delta (8…15), circuit 1
4
…
…
…
…
20
14
delta (56…63), circuit 1
4
21
15
LPF (0…7), circuit 1
4
…
…
…
…
28
22
LPF (56 … 63), circuit 1
4
29
23
reserved
4
…
…
…
…
36
30
reserved
4
37
31
ec-flags (high), circuit 2
4
38
32
ec-flags (low), circuit 2
4
39
33
delta (0…7), circuit 2
4
40
34
delta (8…15), circuit 2
4
…
…
…
…
46
40
delta (56…63), circuit 2
4
47
41
LPF (0…7), circuit 2
4
…
…
…
54
48
LPF (56 … 63), circuit 2
4