AS-i/PROFIBUS-Gateway
Command Interface
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Is
s
ue dat
e -
12.
8.
2007
121
Result: See chapter 10.2.1 "Values for results"
To get the input data again, the T-bit has to be reset again. If a command of the
command interface with DP V1 is being carried out, setting the toggle bit is not
necessary.
10.5.2
Store current configuration to the AS-i master
1. Switch master to configuration mode
2. Write the current slave configuration to the master
3. Switch master to protected mode
4. Wait until master is in normal (protected) operation mode
12-byte management
1. Switch master to config mode
Byte 4
00
hex
…
…
Byte 12
00
hex
Response
Byte 1
50
hex
Byte 2
80
hex
(toggle bit, master1)
Byte 3
16-bit channel 1 high byte
hex
Byte 4
16-bit channel 1 low byte
hex
Byte 5
16-bit channel 2 high byte
hex
Byte 6
16-bit channel 2 low byte
hex
Byte 7
16-bit channel 3 high byte
hex
Byte 8
16-bit channel 3 low byte
hex
Byte 9
16-bit channel 4 high byte
hex
Byte 10
16-bit channel 4 low byte
hex
Byte 11
00
hex
not used
Byte 12
00
hex
not used
Request: SET_OP_MODE
Byte 1
0C
hex
(SET_OP_MODE)
Byte 2
00
hex
(T = 0, master 1, single master)
Byte 3
01
hex
(= config mode)
Byte 4
00
hex
…
…
Byte 12
00
hex
Request