![Pepperl+Fuchs VBG-PB-K20-DMD-C1 Manual Download Page 140](http://html1.mh-extra.com/html/pepperl-fuchs/vbg-pb-k20-dmd-c1/vbg-pb-k20-dmd-c1_manual_1527750140.webp)
AS-Interface
Appendix: Example for startup on a Siemens S7
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Is
s
ue dat
e -
12.
8.
2007
138
12
Appendix: Example for startup on a Siemens S7
This example shows you how to start up the AS-i/PROFIBUS-Gateway stainless
steel version VBG-PB-K20-DMD on a Siemens S7-300 programmable logic con-
troller.
Hardware used:
SIMATIC S7 power supply
PS 307 5A
SIMATIC S7-CPU with PROFIBUS DP
CPU 315-2DP
Order No.: 6ES7 315-2AF03-0AB0
Firmware Version 1.2
AS-i/PROFIBUS-Gateway
VBG-PB-K20-DMD
in stainless steel
AS-i-Power-Extender
AS-i-4E Module
AS-i-4E Module
Power supply
Powers the AS-i components
through the AS-i Power Extender
Software used:
GSD-File for the AS-i/PROFIBUS-Gateway in stainless steel VBG-PB-K20-DMD
SIMATIC Step7 Version 5.2 Service Pack 1 Version: K5.2.1.0
Associated documentation:
AS-i/PROFIBUS-Gateway Operating Manual
SIEMENS S7-300 documentation
12.1
Hardware configuration
12.1.1
Electrical connection for AS-i
To supply the AS-i circuit, connect the output on the AS-i Power Extender or an
AS-i power supply to the AS-i/Profibus-Gateway. Observe correct polarity of the
terminals AS-i(+) and AS-i(-).
In the following the desired AS-i slaves are connected to the AS-i circuit.
The AS-i slaves have their device address set to 0 by default. This must be
changed to the desired AS-i slave address.
You can set the AS-i slave address using the function "AS-INTERFACE SLAVE
ADDR" function from the submenu "SETUP" on the AS-i/Profibus Gateway. For
more detailed information, refer to chapter 6.
Once the AS-i circuit has been configured and parameterized as desired, apply
this configuration to the AS-i/PROFIBUS Gateway using the function "QUICK
SETUP".