![Pepperl+Fuchs IC-KP-B7-V95 Manual Download Page 79](http://html.mh-extra.com/html/pepperl-fuchs/ic-kp-b7-v95/ic-kp-b7-v95_manual_1527931079.webp)
Appendix A
20
13
-0
4
79
A command confirmation appears in the input field:
2
Byte 8
Command code
04h
Command
CT
(Change tag)
Byte 9
Channel/Toggle bit
00h
The element defined the
channel.
Toggle bit = 0
Byte 10
Tag type (high byte)
30h
IPC 03
Byte 11
Tag type (low byte)
33h
IPC 03
byte 12
00h
Not used
Byte 13
00h
Not used
Byte 14
00h
Not used
Byte 15
00h
Not used
3
Byte 16
...
Byte 23
00h
No commands are
transmitted to channel 3.
4
Byte 24
...
Byte 31
00h
No commands are
transmitted to channel 4.
Ele-
ment
Implicit
telegram
Use
Con-
tents
Description
1
Byte 0
Command code (Echo)
04h
Command
CT
(Change tag)
Byte 1
Channel/Toggle bit
02h
Channel = element = 1
Toggle bit = 0
Byte 2
Status
FFh
Processing command.
Byte 3
Reply counter
01h
For every IDENT telegram,
the value on the reply counter
increases by 1.
Byte 4
00h
Byte 5
00h
Byte 6
00h
Byte 7
00h
Ele-
ment
Implicit
telegram
Use
Con-
tents
Description