![Pepperl+Fuchs IC-KP-B7-V95 Manual Download Page 17](http://html.mh-extra.com/html/pepperl-fuchs/ic-kp-b7-v95/ic-kp-b7-v95_manual_1527931017.webp)
Installation
20
13
-0
4
17
5.4.2
Read/Write Head and Trigger Sensors
A maximum of 4 read/write heads can be connected to the IDENTControl.
Instead of the read/write heads, a maximum of 2 trigger sensors can be
connected to sockets 3 and 4. A trigger sensor can be assigned to only one
read/write head. The trigger sensors must be PNP.
Connect the read/write heads and trigger sensors to the sockets on the top of the
enclosure using M12 connectors.
For details of compatible read/write heads, and of compatible connecting cables,
see chapter 4.7.1.
5.4.3
Cable length between control interface and R/W heads
The maximum cable length between the control interface and a connected R/W
head is 1000 meters. If you wish to attain the maximum possible cable length,
select a suitably large cable cross-section. See chapter 4.7.1
5.4.4
Ground connection
The ground connection of the IDENTControl is located at the lower right of the
connector array. The ground conductor is screwed to the housing with a crimp
connector. In order to guarantee safe grounding, the serrated washer must be
mounted between the crimp connector and the housing.
A cross-section of at least 4 mm
2
is recommended for the ground conductor lead.
trigger switch
trigger sensor
read/write head
signal
socket at housing
2
1
3
4
5
+
A
-
+
-
B
1
2
3
4
5
1
Housing
2
Serrated lock washer
3
Crimp connector
4
Lock screw
1
2
4
3