PROFIBUS Power Hub Segment Coupler 3 (SK3)
Troubleshooting
2
016-
10
63
PA bus master parameters are write-
protected.
Built-in slave was addes to the cyclic data
exchange, using the PA bus configuration
module.
Remedy: Use different module to configure
cyclic data exchange.
PA slaves do not take part in cyclic data
exchange.
Add built-in slave to cyclic data exchange.
Unusual gateway behavior and diagnostic
messages recurring at irregular intervals.
Possible cause: Address collision with master
of backup gateway (address 2).
Remedy: Change address of the colliding
slave.
Symptom
Remedy/Background