2
016-
10
16
PROFIBUS Power Hub Segment Coupler 3 (SK3)
Product Specifications
HD2-GTR-4PA
MB-FB-GTR1*
Standard conformity
Electrical isolation
IEC 62103
Electromagnetic compatibility
NE 21:2011
Degree of protection
IEC 60529
Fieldbus standard
IEC 61158-2
Shock resistance
EN 60068-2-27
Vibration resistance
EN 60068-2-6
System Overview
Supply
Rated voltage
19.2 ... 35 V DC
Rated current
160 ... 90 mA
Power dissipation
3 W
Fieldbus interface
PROFIBUS DP
Connection
9-pin Sub-D socket
Protocol
PROFIBUS DP V1
Electrical isolation
CH/PROFIBUS DP
functional insulation acc. to IEC 62103, rated insulation
voltage 50 V
eff
PROFIBUS DP/Supply
CH/CH
All circuits/FE
Data for application in connection with Ex-areas
Statement of conformity
TÜV 04 ATEX 2500 X
Group, category, type of
protection, temperature class
II 3 G Ex nA IIC T4 Gc
Directive conformity
Directive 94/9/EC
EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-
15:2010
International approvals
FM approval
CoC 3024816, CoC 3024816C
Approved for
Class I, Division 2, Groups A, B, C, D, T4 / Class I, Zone 2,
AEx/Ex nA IIC T4
IECEx approval
IECEx TUN 13.0038X
Approved for
Ex nA IIC T4 Gc
Supply
Rated voltage
19.2 ... 35 V SELV/PELV
Rated current
2 ... 3 A
Indicators/operating means
System Overview