PROFIBUS Power Hub Segment Coupler 3 (SK3)
Product Specifications
2
016-
10
15
Figure 2.5
HD2-GTR-4PA component identity
2.7
Technical Data
HD2-GTR-4PA Component Overview
1
Quick Lok bar
2
LED "PWR":
- Green: Power on
3
LED "DP/ERR":
- Red flashing at 2 Hz: DP error
- Red constant: Hardware error
4
LED "Redundancy":
- Yellow constant: Redundancy operation (this gateway module is the primary device)
- Yellow flashing at 2 Hz: Synchronization or redundancy are not available (this gateway
module is the primary device)
- LED off: Single operation (simplex). In redundant mode, this gateway module is the sec-
ondary device
5
LED Seg 1 ... Seg 4:
- Red, flashing at 2 Hz: PA error
- Any segment LED in combination with LED "DP/ERR" on: MAU hardware error
6
PROFIBUS DP interface
PROFIBUS
DP/P A
Gateway
HD2-
GTR-
4P A
Seg4
Seg3
Seg2
Seg1
PWR
DP/
ERR
Red.
1
5
1
4
6
3
2
System Overview
Ambient conditions
Ambient temperature
-40 ... 60
°
C (-40 ... 140
°
F)
Storage temperature
-40 ... 85
°
C (-40 ... 185
°
F)
Relative humidity
< 95 % non-condensing
Shock resistance
15 g 11 ms
Vibration resistance
1 g , 10 ... 150 Hz
Pollution degree
max. 2, according to IEC 60664
Corrosion resistance
acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protection
IP20
Mounting
motherboard mounting