PROFIBUS Power Hub Segment Coupler 3 (SK3)

Troubleshooting

 2

016-

10

61

11.3

Fault Indicated via DCS

PA bus master parameters 

(WD mode, WD time, no. of 

retries, segment no.) cannot 

be written.

PA bus master parameters are 

write-protected. Reason: Built-

in slave is in cyclic data 

exchange using PA bus 

configuration module.

Use different module to 

configure cyclic data 

exchange.

Diagnostic module error or 

module missing.

Diagnostic module is defect or 

was removed (by active ADM 

alarm observer only).

Replace diagnostic 

module 

Switch off ADM alarm 

observer

ADM reports system 

maintenance required.

At least one monitored system 

value has violated the preset 

limit.

Perform diagnostics with the 

DTM diagnostic manager for 

detailed information.

For further information see the 

documentation on the 

"Advanced Diagnostic Module 

HD2-DM-A".

ADM reports system out of 

specification.
ADM reports segment 

maintenance required.
ADM reports segment out of 

specification.

Symptom

Possible cause

Remedy

Note!
First Checks concerning the DCS

In case faults are indicated via the control system, make sure the built- in slaves of your 

PROFIBUS Power Hub system are correctly integrated into the engineering tool.

Symptom

Possible cause

Remedy

PA slaves keep leaving cyclic 

data exchange.

Termination problem on 

PA side

Fault on PA bus 

Poor signal quality on 

PA side

Watchdog time too short

Check termination

Eliminate fault on PA bus 

Perform physical layer 

diagnostics on PA side 

with advanced diagnostic 

module

Increase watchdog time

PA slaves and DP slaves keep 

leaving cyclic data exchange.

Fault on DP bus

Poor signal quality on 

DP side

Eliminate fault on DP bus

Check DP signal quality

Device diagnostics: No 

redundancy even though 

2 gateway modules are used.

Poor signal quality

Gateway module is 

defective

Perform physical layer 

diagnostics on the PA side 

with the advanced 

diagnostic module.

Send gateway to  

Fuchs.

Device diagnostics: 

"Redundancy partner 

missing"

No second gateway 

module plugged into 

motherboard

Secondary gateway 

module has failed

Plug second gateway 

module into motherboard

Replace second gateway 

module

Summary of Contents for FieldConnex Segment Coupler 3

Page 1: ...PROFIBUS Power Hub Segment Coupler 3 SK3 With HD2 GTR 4PA Gateway PROCESS AUTOMATION MANUAL...

Page 2: ...ry for Products and Services of the Electrical Indus try published by the Central Association of the Electrical Industry Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in its most recent...

Page 3: ...ons 18 3 Installation and Commissioning 19 3 1 Mounting and Dismounting 19 3 2 Shielding Grounding 21 3 2 1 Connection to Equipotential Bonding System 21 3 3 Connections 23 4 Hazardous Area Installati...

Page 4: ...40 6 3 5 PROFIBUS PA Retry Limit in the Device Type Manager 41 6 3 6 Restart Functions Redundancy Switchover and Firmware Update 41 6 4 Redundant Operation 44 7 Advanced Diagnostics with the PROFIBUS...

Page 5: ...tion of conformity Certificates Control drawings Additional documents 1 2 Target Group Personnel Responsibility for planning assembly commissioning operation maintenance and dismounting lies with the...

Page 6: ...ymbols Action This symbol indicates a paragraph with instructions You are prompted to perform an action or a sequence of actions Danger This symbol indicates an imminent danger Non observance will res...

Page 7: ...m environments that are compliant to industry standard PROFIBUS DP masters The FieldConnex PROFIBUS Power Hub system has a modular design A number of possible combinations is available in order to mee...

Page 8: ...ring operation Measurement data and alarms are transmitted to the control room This way they make the fieldbus physical layer visible which can now be treated as an active component in plant asset man...

Page 9: ...The simplex Power Hub version features 4 power supply slots the redundant Power Hub version 8 power supply slots PROFIBUS PA segments can receive redundant power supplies if a redundant Power Hub moth...

Page 10: ...Zone 1 The power supply modules provide full galvanic isolation between the bulk power supply and the PA segments The modules offer system reliability for applications where cabling and wiring are ro...

Page 11: ...t www pepperl fuchs com 2 5 Recommended System Combinations Simplex Power Feed for 4 Segments with Gateway Redundancy Figure 2 1 MBHC FB 4 HSC motherboard for the simplex supply of 4 segments combined...

Page 12: ...TR 4PA for simplex gateway coupling The one board simplex system with single gateway coupling consists of the following components Combined Power Hub gateway motherboard MBHC FB 4 GT HD2 GTR 4PA x 1 P...

Page 13: ...BHC FB 4R HSC HD2 GTR 4PA x 2 Power supply modules x 8 Sub D cable 9 pins Optional components Diagnostic module Surge protectors TPH LBF IA1 36 DE x 4 Earth bar for surge protectors ACC LBF EB 4 PROFI...

Page 14: ...ent Overview 1 Motherboard MB FB GTR1 2 Gateway HD2 GTR 4PA 3 Connections Volt free contact alarm and diagnostic bus Diagnostic link cable ACC MB HDC optional accessory 4 Sub D interface for the conne...

Page 15: ...operation simplex In redundant mode this gateway module is the sec ondary device 5 LED Seg 1 Seg 4 Red flashing at 2 Hz PA error Any segment LED in combination with LED DP ERR on MAU hardware error 6...

Page 16: ...l isolation CH PROFIBUS DP functional insulation acc to IEC 62103 rated insulation voltage 50 Veff PROFIBUS DP Supply CH CH All circuits FE Data for application in connection with Ex areas Statement o...

Page 17: ...EN 60079 11 2012 International approvals IECEx approval IECEx TUR 16 0007X Approved for Ex ec IIC T4 Gc Accessories ACC MB HDC Diagnostic link cable length 6 cm ACC MB HGC Sub D cable 9 pins for conne...

Page 18: ...0 18 PROFIBUS Power Hub Segment Coupler 3 SK3 Product Specifications 2 8 Dimensions Figure 2 6 All dimensions in millimeters and without tolerance indication Component Dimensions 39 mm 166 mm 135 mm 1...

Page 19: ...fficiently suitable enclosure dust water or other external interferences can cause the live device to spark The sparks can ignite the surrounding potentially explosive atmosphere Only mount the device...

Page 20: ...Push down the red Quick Lok bars on each side of the module to fix it to the panel No tools required The new module has been installed Dismounting Modules from the Motherboard To dismount a module fro...

Page 21: ...necting the Ground Connection Cable 1 Connect the ground cable to a cable lug 2 Position the cable lug over the ground connection clamp with the cable pointing downwards Tip Earth Connection Ensure th...

Page 22: ...between screw lug and clamp as illustrated Figure 3 2 Connecting the ground connection cable 4 Tighten the screw with a torque of 1 5 Nm The cable lug is properly attached and cannot come loose Conne...

Page 23: ...tions Connections 1 PROFIBUS DP connection 2 PROFIBUS DP connection 3 Grounding terminal 4 Connections Volt free contact alarm and diagnostic bus Diagnostic link cable ACC MB HDC optional accessory 5...

Page 24: ...nal accessory 7 Final motherboard link optional 3 4 5 7 6 1 2 Note Different Ways to Transmit Diagnostic Information By default diagnostic information from the diagnostic module HD2 DM is transmitted...

Page 25: ...ere Only mount the device in an enclosure with degree of protection IP54 according to IEC EN 60529 The enclosure must have an EU declaration of conformity according to the ATEX Directive for at least...

Page 26: ...y HD2 GTR 4PA proceed as follows 1 In order to assign the required 3 digit address of the built in slaves Set the control switches to the correct positions 2 In order to restart the gateway Disconnect...

Page 27: ...is also applies to start up and configuration The GSD file must be integrated in a configuration tool before it can be used to configure and operate a PROFIBUS PA slave Before converting GSD files alw...

Page 28: ...E function is disabled SYNC function is disabled These functions are used with PROFIBUS DP to synchronize sensors actuators It is possible that these functions do no longer work correctly because oper...

Page 29: ...nterval in the cyclic data exchange process or user data exchange to ensure that the PROFIBUS master is still active This socalled watchdog time TWD is measured in the PROFIBUS slave If the response m...

Page 30: ...This is determined as follows The follwing 2 types of watchdogs can be configured on the HD2 GTR 4PA in cyclic or acyclic data exchange see chapter 6 3 4 Transparent watchdog The watchdog time on the...

Page 31: ...2 Latest version of the HD2 GTR 4PA DTM 40 MB free hard drive storage Installing the DTM Package with PACTwareTM Example In order to install the DTM package on your system proceed as follows 1 Install...

Page 32: ...lows 1 Start PACTwareTM Note Make sure the latest DTM version is installed and that the device catalog is updated 2 Open the appropriate project or create a new one 3 Open the Device catalog View Devi...

Page 33: ...ave Address in the DTM In order to enter the built in slave address that was assigned on the gateway motherboard into the DTM proceed as follows 1 Right click on PROFIdtm DPV1 in the project tree and...

Page 34: ...In order to integrate a HD2 DM A ADM via PROFIBUS PA proceed as follows 1 In the Device catalog open PEPPERL FUCHS GmbH Device HD2 DM A 2 Drag and drop HD2 DM A into the HD2 GTR 4PA node of the the pr...

Page 35: ...as an integrated slave a socalles built in slave BIS with a DP address that can be configured with the DIP switch on the motherboard As a device participating in cyclic data exchange the BIS returns f...

Page 36: ...T_DIAG to be set in the slave diagnostics The process control system then marks that slave as defective Channel diagnostics returns specific diagnostic information on each individual segment These err...

Page 37: ...PA communication are time incompatible they are not relevant for practical purposes Identification Maintenance I M functions are supported 6 3 Acyclic Data Exchange with Built In Slave via Device Type...

Page 38: ...to the device icon in the project tree indicates that the connection exists Opening the Offline Dialog In order to open the Offline dialog proceed as follows 1 Right click in the project tree on HD2 G...

Page 39: ...above 2 In the DTM header press the Print button The Print preview window of the diagnostic report appears 3 In the footer of the Print preview window click Print The Printer driver selection menu ap...

Page 40: ...uration Slave Bus Parameter Set System Settings Channel Assignment HD2 GTR 4PA Online Tag Location Descriptor Signature Segment Tags 1 4 Activated PA Segments ADM Settings ADM Alarm Observer PA Retry...

Page 41: ...ic data exchange Setting the PA Retry Limit in the DTM In order to set the PA retry limit in the DTM proceed as follows 1 Open the Online or Offline dialog 2 Select the retry limit from the drop down...

Page 42: ...nsure that redundancy is available The primary and secondary device exchange roles The active built in slave drops out of communication All coupled PA slaves remain in the data exchange Redundancy Beh...

Page 43: ...PROFIBUS Power Hub Segment Coupler 3 SK3 Operation 2016 10 43 4 Choose the new firmware file 5 Confirm the installation windows which follow by clicking Continue 6 Restart the gateway...

Page 44: ...n redundant masters The built in slave automatically detects whether the DP master is using a redundancy concept If the DP master is working according to the flying redundancy concept the gateway auto...

Page 45: ...e in operation with no errors Both gateways detect DP baud rates No errors occurred in PA communication If redundant operation is not available this is reported back by the slave diagnostics Possible...

Page 46: ...way Note The reinstalled gateway normally takes all configurations from the primary gateway Any previous configurations of the new gateway are overwritten The primary and secondary built in slaves are...

Page 47: ...mentation of the Advanced Diagnostic Module HD2 DM A In order to integrate the advanced diagnostic module HD2 DM A into a PROFIBUS Power Hub installation one of the following 2 different kind of setup...

Page 48: ...ndow the so called system diagnostic window You can find further information regarding the FDS and the setup configuration and commissioning of the diagnostic module corresponding documentation of the...

Page 49: ...ption Operator application Application on which the plant management or operator system is running An OPC DA client can also be running here Maintenance application Host application for the FDT frame...

Page 50: ...the Alarm Observer in the Device Type Manager 1 Open the window Offline or online parameterization 2 Choose Alarm Observer Enabled from the drop down list and confirm with Return Interface Descriptio...

Page 51: ...Advanced Diagnostic Messages in the Gateway DTM Due to the integration of basic alarms and warnings into the slave diagnostics of the gateway the DTM diagnostics dialog of the gateway includes the fo...

Page 52: ...is concept connects both slave and master instances to the same physical bus so only 1 PROFIBUS DP cycle exists The address of the primary slave incremented by 64 is assigned to the backup slave Figur...

Page 53: ...cy Concepts Figure 8 2 Flying redundancy with redundancy link modules RLM for combination with media redundancy This structure represents a common flying redundancy concept with no need for the primar...

Page 54: ...own PROFIBUS cycle on 2 different lines The redundant slave instances are connected to each other with the corresponding connection lines Figure 8 3 System redundancy This concept has the disadvantage...

Page 55: ...for configuration of a device DTM Common abbreviation for device type manager Software which allows parameterization and diagnostics of field devices via a GUI Parameterization can be done online i e...

Page 56: ...ply field devices retry limit Number of retries that are undertaken before a field device is interpreted as non existent by the host RS 485 Communication protocol on the PROFIBUS DP segment Segment Pr...

Page 57: ...n motherboard 0 left device 1 right device 0 for non redundant motherboard Total status Combined device status message good 0 x 00 bad 0 x 80 Number of activated PA segments Number of active PA segmen...

Page 58: ...5 Redundancy communication status only with redundant layout 0 OK 1 Redundancy link error 6 DP baud rate status 0 OK 1 No baud rate detected 7 Built In slave status 0 OK 1 Built in slave not in data...

Page 59: ...uble slave address other device or BIS 3 Reserved 4 Master diagnostic status 0 OK 1 PA master not in token ring 5 Hardware state 0 OK 1 Segment MAU error 6 Segment maintenance required 0 False 1 True...

Page 60: ...is flashing red No data transmission on DP side Master problem Gateway defective Check cables Check termination Check master Restart gateway If problem persists send gateway to Pepperl Fuchs LED DP ER...

Page 61: ...ateway modules are used Gateway module is defective Send gateway to Pepperl Fuchs Symptom Possible cause Remedy Symptom Possible cause Remedy Redundancy switchover occurs for no apparent reason Built...

Page 62: ...ossible cause Remedy Note First Checks concerning the DCS In case faults are indicated via the control system make sure the built in slaves of your PROFIBUS Power Hub system are correctly integrated i...

Page 63: ...side Harmonize number of PA segments at gateway and actual number of existing segments Perform physical layer diagnostics on PA side with advanced diagnostic module Diagnostic module error or module...

Page 64: ...ion module Remedy Use different module to configure cyclic data exchange PA slaves do not take part in cyclic data exchange Add built in slave to cyclic data exchange Unusual gateway behavior and diag...

Page 65: ...rl fuchs com Worldwide Headquarters Pepperl Fuchs GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com For the Pepperl Fuchs representative closest to you check www pepperl fu...

Reviews: