Model 1011

 

Installation and Operation Manual

18

Par

t No

. 51

2083  Dra

wing No

. 1

29-0205a  03/09

System Maintenance

Regular Maintenance

Drain the protection system regulator frequently and clean system with nonsolvent cleaning agents only.

Long-Term Maintenance

Calibrate the enclosure pressure indicator to 0 inches by venting the purge pressure reference port and the protected enclosure to 

atmosphere and adjusting the calibration screw in the lower center portion of the indicator’s face.
Fully open the enclosure pressure control regulator, to blow out any deposits around the tip of the valve and to ensure that the 

enclosure protection vent is operating properly, then carefully readjust system according to the set-up procedure and operating 

sequence on pages 14 and 15. Replace or tighten stem packing nut as required to prohibit stem packing leakage.
Carefully disassemble the enclosure protection vent by loosening the two bottom hex nuts that hold the unit together.

(DO NOT REMOVE CAP NUTS ON TOP OF VENT BODY)

Carefully clean the flapper valve and vent body seats with warm soap and water, being careful not to extend the vent valve beyond 

its normal opening point, and being careful not to exert any stress on the valve hinge.
Examine the entire protection system and the protected enclosure(s), and replace any defective parts during routine shutdown of 

the protected enclosure(s). Parts are available from Fuchs on immediate notice as required.

MAINTENANCE SCHEDULE

Date

Work performed

Performed by

Summary of Contents for 1011 Series

Page 1: ...MODEL 1011 TYPE Z PURGE PRESSURIZATION SYSTEM PROCESS AUTOMATION INSTALLATION AND OPERATION MANUAL...

Page 2: ...ive heat utilize combustible gas or expose arcing contacts to the hazardous atmosphere in Type 4 or 12 enclosures in the place of explosion proof Type 7 enclosures Other purposes include heat moisture...

Page 3: ...closure pressure control regulator 513315 002000 1 Installation operation manual 129 0205 1 Enclosure warning nameplate CI 513008 EWN 1 1 Enclosure warning nameplate CII 513009 EWN 2 Please call and r...

Page 4: ...erials such as materials designed to meet or exceed ANSI UL94 ratings of 94 V 0 or 94 5V Adjacent Enclosures 1 Adjacent enclosures must be protected by one of the following means a purged or pressuriz...

Page 5: ...verview PROTECTIVE GAS SUPPLY SYSTEM SUPPLY TUBING ELECTRICAL ALARM WIRING CONDUIT SEAL SERVICE VALVE SYSTEM SUPPLY FITTING ENCLOSURE PROTECTION SYSTEM SYSTEM MOUNTING BOLT ENCLOSURE SUPPLY TUBING ENC...

Page 6: ...ure protection system the enclosures must be connected in series from the smallest to the largest to ensure adequate protective gas flow PROTECTED ENCLOSURE C B ENCLOSURE PROTECTION VENT Optional E SU...

Page 7: ...nded surface 4 Check for obstructions hindering bolt fastening drill and ream the mounting holes before mounting the system 5 Secure the system to the enclosure or other mounting surface using the fas...

Page 8: ...8 8 25 8 8 25 8 8 Panel Cutout 7 Panel Cutout 7 3 25 1 25 6875 7 3125 8 875 2 4375 25 O D TYP 2 System Mounting Plate 8 25 8 1011 LH Left hand configuration 1011 RH Right hand configuration 1011 TM To...

Page 9: ...inent position on or near all enclosure accesses doors and covers One 1 EWN is provided with each system located in the manila envelope taped to the mounting flange of the system Additional EWNs are a...

Page 10: ...LOSURE CONNECTION FITTING Pneumatic Connection Requirements ALL FITTINGS MAY BE CUSTOMER OR FACTORY FURNISHED 1 For system supply one 1 SC 4 1 4 male straight connector or one 1 NC 4 1 4 male elbow co...

Page 11: ...tting manufacturer s specifications Secure tubing to appropriate structural supports as required Tubing PM Configurations Enclosure bulkhead fittings 1 Select the fittings required to install the syst...

Page 12: ...ce Supply Enclosure reference bulkhead fitting Enclosure supply bulkhead fitting Enclosure pressure gauge Enclosure reference inlet Venturi orifice Mounting bracket System supply inlet Enclosure press...

Page 13: ...larm and the enclosure IMPORTANT NOTE NFPA 496 requires the use of an alarm or an indicator to detect the loss of safe enclosure pressure In addition the NFPA 496 requires that if an indicator alone i...

Page 14: ...rators withhold power to the enclosure while inducing Class I exchange for at least five 5 minutes Normal exchange time calculations should be doubled if large obstructions block inert gas flow The st...

Page 15: ...f protected equipment power 6 Excessively hot equipment must be isolated in a separate protected enclosure unless the enclosure is marked with a warning which indicates a required cool down time perio...

Page 16: ...drifts up or down from the safe pressure setting Application involves a small tightly sealed enclosure and or a fluctuating protective gas supply Pre regulate the protective gas supply upstream of the...

Page 17: ...MITED WARRANTY SET FORTH HEREIN IS THE ONLY WARRANTY MADE BY P F WITH RESPECT TO THE PRODUCTS IT IS EXPRESSLY AGREED AND UNDERSTOOD THAT P F MAKES NO WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTI...

Page 18: ...properly then carefully readjust system according to the set up procedure and operating sequence on pages 14 and 15 Replace or tighten stem packing nut as required to prohibit stem packing leakage Ca...

Page 19: ..._________________________________________________________ Notes _ _______________________________________________________________________________________________ ______________________________________...

Page 20: ...ost demanding needs of industry Resulting from our world wide presence and our high flexibility in production and customer service we are able to offer complete individual solutions wherever and whene...

Reviews: