Pneumatic Tubing Requirements

Protective Gas Supply Requirements

The protective gas supply to the protection system must be a 

clean, instrument quality compressed air or nitrogen and must 

contain no more than trace amounts of flammable gas, vapor 

or dust.
The protective gas supply compressor intake must originate 

in a nonhazardous location. Suction duct passing through a 

hazardous location and the protection system tubing and piping 

must be fabricated from noncombustible materials suitable for 

prevailing hazards and environmental conditions. 
The protective gas supply must originate from a dedicated 

instrument quality compressed air header (1/2" pipe or larger), 

no farther than twenty (20) feet from the protection system. 

Local compressors and gas cylinders should not be used 

before consulting with Fuchs.
The protective gas supply to the protection system must be 

equipped with a tamper-proof regulator set at 5 psi maximum.

Exception:

 If the protected enclosure(s) is equipped with an 

Enclosure Protection Vent, the protective gas supply to the 

protection system must not exceed 120 psi maximum, 5 psi 

minimum. (See page 3, "System Specifications" for additional 

information concerning protective gas supply requirements.)

SC-4

NC-4

EBC-4

EFC-4

EPC-10

SYSTEM SUPPLY FITTINGS

ENCLOSURE SUPPLY & REFERENCE FITTINGS

MULTIPLE ENCLOSURE CONNECTION FITTING

Pneumatic Connection Requirements

ALL FITTINGS MAY BE CUSTOMER OR FACTORY FURNISHED

1. For system supply, one (1) SC-4 1/4" male straight

connector or one (1) NC-4 1/4" male elbow connector or

equivalent fitting per system.

NOTE: Above fitting is required only if protection system

is furnished with an optional in-line filter kit (model ILFK)

accessory.

One (1) similar fitting which will connect the inert gas supply

tubing to the inert gas supply header connection point and

one (1) lot of 1/4" O.D., .035" wall thickness, welded or

seamless stainless steel tubing.

2. For enclosure supply, one (1) EFC-4 1/4" flush connector,

or one (1) EBC-4 1/4" feed-through connector or equivalent

fitting per system.

3. For enclosure reference, one (1) EFC-4 1/4" flush connector,

or one (1) EBC-4 1/4" feed-through connector or equivalent

fitting per system.

4. One (1) lot of 1/4" O.D., .035" wall thickness, welded or

seamless stainless steel tubing.

5. For multiple enclosure connections, two (2) EPC-10 1/2"

pipe mounting hubs or equivalent and 1/2" 150# rated pipe

couplings & unions per interconnection.
One (1) lot 150# rating 1/2" galvanized or aluminum pipe

and fittings, fully reamed and unrestricted.

PM Pneumatic Connection Requirements

In addition to item numbers 1, 4, and 5 above, the following 

fittings are required for all PM configurations. 
1. For system supply on PM configurations, one (1) additional

EBC-4 or equivalent 1/4" through bulkhead fitting per

system is required.

2. For atmospheric reference, one (1) PRB-4 or equivalent 1/4"

female bulkhead fitting and stainless steel sintered element

is required.

PRB-4

SYSTEM ATMOSPHERIC REFERENCE FITTING

Summary of Contents for 1011 Series

Page 1: ...MODEL 1011 TYPE Z PURGE PRESSURIZATION SYSTEM PROCESS AUTOMATION INSTALLATION AND OPERATION MANUAL...

Page 2: ...ive heat utilize combustible gas or expose arcing contacts to the hazardous atmosphere in Type 4 or 12 enclosures in the place of explosion proof Type 7 enclosures Other purposes include heat moisture...

Page 3: ...closure pressure control regulator 513315 002000 1 Installation operation manual 129 0205 1 Enclosure warning nameplate CI 513008 EWN 1 1 Enclosure warning nameplate CII 513009 EWN 2 Please call and r...

Page 4: ...erials such as materials designed to meet or exceed ANSI UL94 ratings of 94 V 0 or 94 5V Adjacent Enclosures 1 Adjacent enclosures must be protected by one of the following means a purged or pressuriz...

Page 5: ...verview PROTECTIVE GAS SUPPLY SYSTEM SUPPLY TUBING ELECTRICAL ALARM WIRING CONDUIT SEAL SERVICE VALVE SYSTEM SUPPLY FITTING ENCLOSURE PROTECTION SYSTEM SYSTEM MOUNTING BOLT ENCLOSURE SUPPLY TUBING ENC...

Page 6: ...ure protection system the enclosures must be connected in series from the smallest to the largest to ensure adequate protective gas flow PROTECTED ENCLOSURE C B ENCLOSURE PROTECTION VENT Optional E SU...

Page 7: ...nded surface 4 Check for obstructions hindering bolt fastening drill and ream the mounting holes before mounting the system 5 Secure the system to the enclosure or other mounting surface using the fas...

Page 8: ...8 8 25 8 8 25 8 8 Panel Cutout 7 Panel Cutout 7 3 25 1 25 6875 7 3125 8 875 2 4375 25 O D TYP 2 System Mounting Plate 8 25 8 1011 LH Left hand configuration 1011 RH Right hand configuration 1011 TM To...

Page 9: ...inent position on or near all enclosure accesses doors and covers One 1 EWN is provided with each system located in the manila envelope taped to the mounting flange of the system Additional EWNs are a...

Page 10: ...LOSURE CONNECTION FITTING Pneumatic Connection Requirements ALL FITTINGS MAY BE CUSTOMER OR FACTORY FURNISHED 1 For system supply one 1 SC 4 1 4 male straight connector or one 1 NC 4 1 4 male elbow co...

Page 11: ...tting manufacturer s specifications Secure tubing to appropriate structural supports as required Tubing PM Configurations Enclosure bulkhead fittings 1 Select the fittings required to install the syst...

Page 12: ...ce Supply Enclosure reference bulkhead fitting Enclosure supply bulkhead fitting Enclosure pressure gauge Enclosure reference inlet Venturi orifice Mounting bracket System supply inlet Enclosure press...

Page 13: ...larm and the enclosure IMPORTANT NOTE NFPA 496 requires the use of an alarm or an indicator to detect the loss of safe enclosure pressure In addition the NFPA 496 requires that if an indicator alone i...

Page 14: ...rators withhold power to the enclosure while inducing Class I exchange for at least five 5 minutes Normal exchange time calculations should be doubled if large obstructions block inert gas flow The st...

Page 15: ...f protected equipment power 6 Excessively hot equipment must be isolated in a separate protected enclosure unless the enclosure is marked with a warning which indicates a required cool down time perio...

Page 16: ...drifts up or down from the safe pressure setting Application involves a small tightly sealed enclosure and or a fluctuating protective gas supply Pre regulate the protective gas supply upstream of the...

Page 17: ...MITED WARRANTY SET FORTH HEREIN IS THE ONLY WARRANTY MADE BY P F WITH RESPECT TO THE PRODUCTS IT IS EXPRESSLY AGREED AND UNDERSTOOD THAT P F MAKES NO WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTI...

Page 18: ...properly then carefully readjust system according to the set up procedure and operating sequence on pages 14 and 15 Replace or tighten stem packing nut as required to prohibit stem packing leakage Ca...

Page 19: ..._________________________________________________________ Notes _ _______________________________________________________________________________________________ ______________________________________...

Page 20: ...ost demanding needs of industry Resulting from our world wide presence and our high flexibility in production and customer service we are able to offer complete individual solutions wherever and whene...

Reviews: