Installer Manual Siata V132-SFE-EV-VIRIDION - Commissioning
Ref. MKT-IM-009 / C - 08.06.2018
69 / 110
13. Once in 2C cycle (brine draw) check if the brine is effectively drawn by the valve, and advance to
the next cycle. In case controller is programmed for refill after the regeneration, move it to 5C
cycle (refill) and perform operations described on steps 9 to 11.
14. Press
to move the controller is service position. Open a faucet and run the water for a couple
of minutes, then check the hardness and eventually adjust the residual hardness if valve have a
mixing device.
7.2. Sanitization
7.2.1. Disinfection of water softeners
The construction materials used in modern water softeners do not support bacterial growth, nor will
these materials contaminate a water supply. During normal use, a softener may become fouled with
organic matter, or in some cases with bacteria from the water supply. This may result in an off-taste
or odour in the water.
Thus, your softener may need to be disinfected after installation. Some softeners will require periodic
disinfection during their normal lifetime. Consult your installing dealer for more information on
disinfecting your softener.
Depending on the conditions of use, the softener type, the type of ion exchanger, and the disinfectant
available, a choice can be made from among the following methods.
7.2.2. Sodium or calcium hypochlorite
These materials are satisfactory for use with polystyrene resins, synthetic gel zeolite, greensand and
bentonites.
5.25% Sodium hypochlorite
If stronger solutions are used, such as those sold for commercial laundries, adjust the dosage
accordingly.
Dosage
Polystyrene resin: set 1.25 mL fluid per 1 L of resin.
Non-resinous exchangers: set 0.85 mL fluid per 1 L.
Brine tank softeners
Backwash the softener and add the required amount of hypochlorite solution to the well of the brine
tank. The brine tank should have water in it to permit the solution to be carried into the softener.
Proceed with the normal regeneration.
Calcium hypochlorite
Calcium hypochlorite, 70% available chlorine, is available in several forms including tablets and
granules. These solid materials may be used directly without dissolving before use.
Dosage
Measure two grains ~ 0.11 mL 1 L.
Brine tank softeners
Backwash the softener and add the required amount of hypochlorite to the well of the brine tank. The
brine tank should have water in it to permit the chlorine solution from being carried into the softener.
Proceed with the normal regeneration.
Summary of Contents for SIATA V132-SFE-EV-VIRIDION
Page 1: ...SIATA V132 SFE EV VIRIDION INSTALLER MANUAL WATER PURIFICATION...
Page 77: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 77 110...
Page 79: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 79 110...
Page 81: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 81 110...
Page 83: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 83 110...
Page 85: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 85 110...
Page 87: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 87 110...
Page 89: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 89 110...
Page 91: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 91 110...
Page 110: ...www pentairaquaeurope com...