Installer Manual Siata V132-SFE-EV-VIRIDION - Installation
46 / 110
Ref. MKT-IM-009 / C - 08.06.2018
5.9.
Overflow line connection
In the event of a malfunction, power failure, etc, the brine tank overflow fitting will direct “overflow”
to the drain instead of spilling on the floor. This fitting should be on the side of the cabinet or brine
tank. Most tank manufacturers include a post for the tank overflow connector.
To connect the overflow line, locate the hole on side of tank. Insert overflow fitting into tank and
tighten with plastic thumb nut and gasket as shown below. Attach a length of 12.7 mm (1/2") I.D.
tubing (not supplied) to fitting and run to drain.
Do not elevate overflow higher than overflow fitting.
Do not tie into drain line of controller unit. Overflow line must be a direct, separate line from overflow
fitting to drain, sewer or tub. Allow an air gap as per drain line instructions.
Caution
Floor drain is always recommended to avoid flooding in case of overflow.
5.10. Brine line connection
The brine line from the tank connects to the valve. Make the connections and hand tighten. Be sure
that the brine line is secure and free from air leaks. Even a small leak may cause the brine line to drain
out, and the softener will not draw brine from the tank. This may also introduce air into the valve,
causing problems with the valve operation.
Most installations utilize a tank check valve.
5.11. Chlorinator
The chlorinator is able to carry out automatic sterilisation of the resin during regeneration. To
perform this function, the valve must naturally be equipped with a controller able to manage the
SIATA range of chlorinators. The controller supplies power to the electrolytic cell during the
regeneration cycle to produce an appropriate quantity of chlorine by electrolysis of the brine, which is
necessary for the sterilisation of the resins.
Drain tubing
Overflow fitting
Secure hose in place
Air gap
Drain
Summary of Contents for SIATA V132-SFE-EV-VIRIDION
Page 1: ...SIATA V132 SFE EV VIRIDION INSTALLER MANUAL WATER PURIFICATION...
Page 77: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 77 110...
Page 79: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 79 110...
Page 81: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 81 110...
Page 83: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 83 110...
Page 85: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 85 110...
Page 87: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 87 110...
Page 89: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 89 110...
Page 91: ...Installer Manual Siata V132 SFE EV VIRIDION Maintenance Ref MKT IM 009 C 08 06 2018 91 110...
Page 110: ...www pentairaquaeurope com...