background image

I/O CONNECTIONS

I/O CONNECTIONS

LABEL

FUNCTION

CONNECTION

RATING

AI+

Positive connection for transducer

Red transducer wire

24 Volt 

(supplied)

AI-

Negative connection for transducer

Black transducer wire

V+

Positive side of 24 volt power supply. 

Used to power external devices.

Positive side of 24V external device, 

i.e., flow switch, moisture sensor, 

alternator, etc. Need to complete the 

circuit with V-. See Figures 15 and 17.

40mA 

maximum 

output

V-

Negative side of 24 volt power supply. 

Used to power external devices.

Typically to I1-, I2-, or O1-. Used with 

a flow switch, moisture sensor, 

alternator, etc. Need to complete the 

circuit with V+. See Figures 15 and 17.

I1+

Positive (dry contacts) connection of 

Digital Input 1. Connect when using an 

external device to control Drive. 

From an external device i.e., flow 

switch, moisture sensor, alternator, etc. 

Requires complete circuit connection 

with I1-. See Figures 15 and 16.

Accepts 

24VDC and up 

to 230VAC

I1-

Negative (dry contacts) connection of 

Digital Input 1. Connect when using an 

external device to control Drive.

Can be from V- or from the negative 

side of an external power supply. 

Requires complete circuit connection 

with I1+. See Figures 15 and 16.

I2+

Positive (dry contacts) connection of 

Digital Input 2. Connect when using an 

external device to control Drive.

From an external device, i.e., flow 

switch, moisture sensor, alternator, etc. 

Requires complete circuit connection 

with I2-. See Figures 15 and 16.

I2-

Negative (dry contacts) connection of 

Digital Input 2. Connect when using an 

external device to control Drive.

Can be from V- or from the negative 

side of an external power supply. 

Requires complete circuit connection 

with I2+. See Figures 15 and 16.

O1+

Output relay (dry contacts) 

connection. Programmed to close 

when pump is 

Running

 or 

Faulted

.

Positive wires of an external device. 

See Figures 17 and 18.

Accepts up 

to 5 Amps at 

24VDC and 

8 Amps at up 

to 230VAC

O1+

Output relay (dry contacts) 

connection. Programmed to close 

when pump is 

Running

 or 

Faulted

.

Positive wires of an external device. 

See Figures 17 and 18.

P

Positive connection of an RS-485 

communication device (see Figure 15).  Positive wire from RS-485 device.

Per RS-485 

Standard

N

Negative connection of an RS-485 

communication device (see Figure 15).

Negative wire from RS-485 device.

TABLE 10 - I/O FUNCTION, CONNECTIONS, RATINGS

The I/O terminals are located in the center of 

the wiring compartment, as shown previously 

in Figure 9. 

The Digital Input connections (

I1

 and 

I2

) are 

used to control the Drive based on the state 

of an external device, such as a flow switch, 

moisture sensor, alternator, or other device. 

Programming is needed to activate any of 

these functions (see Table 9).

The Output Relay (

O1

) is used to control an 

external device based on two states of Drive; 

either Running the pump or Faulted. 

Programming is needed to activate any of 

these functions (see Table 9).

Cable Installation

Three 13mm conduit knockouts are provided 

on the bottom of the Drive enclosure for the 

I/O wires.

Break out the closest 13mm knockout and route 

the wires through. Use a cord grip to prevent 

the wire from rubbing and causing a short.

NOTICE

 Never run low voltage I/O wire through 

the same conduit hole as the 230V input wires 

or motor wires.

To connect the external wires to the 

terminals:

1.  Strip wire 13mm

2.  Push spring terminal up with finger    

or slotted screwdriver

3.  Insert wires from bottom

4.  Release spring terminal

Connection Examples

Figures 15-18 show various connection 

schemes for typical applications. Table 10 

describes each I/O terminal, including purpose 

and rating.

6540 0412

Figure 15 - Example Input with internal 
24 volt supply

6542 0412

Figure 17 - Example Output relay with internal  
24 volt supply

6541 0412

115 VAC

or

230 VAC

+

-

Figure 16 - Example external Input with 
external supply

6541 0412

115 VAC

or

230 VAC

+

-

Figure 18 - Example Output with external supply

PENTEK IntelliDrive

 Owner’s Manual

PENTEK IntelliDrive

 Owner’s Manual

17

16

Summary of Contents for PENTEK INTELLIDRIVE PID2000-1123

Page 1: ...SSURE CONTROLLER Should the installer or owner be unfamiliar with the correct installation and or operation of this type of equipment please contact the distributor or manufacturer for the correct advice before proceeding with the installation or operation of this product ...

Page 2: ...age 6 for circuit breaker sizing with no other appliances on the circuit Risk of burns The drive can become hot during normal operation Allow it to cool for 10 minutes after shut down before handling it to avoid burns Risk of electric shock A means for disconnection from the supply mains having a contact separation in all poles must be incorporated in the fixed wiring in accordance with the wiring...

Page 3: ...gnal The Drive senses and processes the signal in the PID Proportional Integration Derivative control When operating in AUTOSTART mode the Drive increases and decreases the speed of the pump motor as needed to maintain constant pressure in the piping system Keypad The keypad programs the Drive monitors the status of the pump and displays faults if they occur Each button has a unique function as de...

Page 4: ...984M 5 5 28 1 33 55 88 Mounting the Drive To mount the Drive as shown in Figure 6 follow this procedure 1 First remove the cover by backing out screw at bottom of front cover 2 Push on backplate with thumbs while pulling the cover toward you with index fingers creating a gap See Figures 3 and 4 3 Pull bottom of cover towards you lift up on cover and remove See Figure 5 Gap Figure 3 Separate cover ...

Page 5: ...ly accepts 230V single phase input power If incoming power does not match this have a qualified electrician alter supply voltage to 230V 1Ph before connecting it to the Drive Terminal Removable pull down 01 01 I1 I1 I2 I2 V V AI AI P N SD CARD Transducer Cable Connections Submersible Motor 3 Ph 3 W 1 Ph follow colors as above Submersible Motor 1 Ph 2 W connect to Y and B any order Above Ground Mot...

Page 6: ... installed before operating the PENTEK INTELLIDRIVE Most installations will only require the initial startup settings However the installer may need to set additional parameters Information about accessing all parameters explanations of their functions and procedures for changing parameter values will be found later in this section 1 Program the Drive Apply power to the PENTEK INTELLIDRIVE Setup G...

Page 7: ...9 lists all available commands and parameters for the PENTEK INTELLIDRIVE 6569 0512 Press PSI Preset Use arrows to change the value Press Enter to Save Press Enter Figure 14 Change PSI Setpoint using PSI Preset 6568 0512 Press Auto Start Use arrows to change the value Press Enter to Save Press Enter Verify Running Fixed Press displayed on screen Figure 13 Change PSI Setpoint while running pump Key...

Page 8: ...VALUE DESCRIPTION DEFAULT MIN MAX Ex Runtime Excessive Runtime Detection _ Enabled Disabled Enabled Enables or disables Excessive Runtime Detection Excessive Runtime Hours Hours 24 1 100 Number of hours Drive can run before it faults on Excessive Runtime Dry Run Auto Restart Delay Minutes 10 Min 3 Min 60 Min Time Drive waits to restart pump when Dry Run is detected Number of Resets 3 0 5 Number of...

Page 9: ...and 8 Amps at up to 230VAC O1 Output relay dry contacts connection Programmed to close when pump is Running or Faulted Positive wires of an external device See Figures 17 and 18 P Positive connection of an RS 485 communication device see Figure 15 Positive wire from RS 485 device Per RS 485 Standard N Negative connection of an RS 485 communication device see Figure 15 Negative wire from RS 485 dev...

Page 10: ...n Possible leak Check for pipe break or large leak Dry running pump Check water level in well Ground Fault Ground wire shorted to motor phase Check the ground wire for short to motor phase wire or check insulation integrity with a megger Long motor cable length If motor cable length is more than 305m a reactor or filter may be needed to limit capacitance between motor wires System Not Grounded Ung...

Page 11: ... Fault Internal voltages are out of range Drive will auto reset and attempt to clear fault Fault Reset can be pressed to clear fault as well Then try to operate pump If fault continues Drive may need replacement Hardware Fault Internal hardware failure Fault Reset can be pressed to clear fault Then try to operate pump If fault continues Drive may need replacement External Fault The external device...

Page 12: ...rial No Dealer Installer Installer Phone No Date of Installation Wire Lengths in Meters Circuit Breaker to Drive PENTEK INTELLIDRIVE to Motor Supply Voltage Note to Installer Record the data listed above for future reference Give manual to end user or attach to PENTEK INTELLIDRIVE when installation is complete OWNER S INFORMATION PENTEK IntelliDrive Owner s Manual 22 ...

Page 13: ...yright law Any reproduction display publication modification or distribution is strictly prohibited without the prior written permission from Pentair Disclaimer Pentair reserves the right to change product specifications and products details All product images are for reference purposes only and may not represent actual and or current product 2022 Pentair All rights reserved ...

Reviews: