PROGRAMMING
PROGRAMMING
MENU
SETTINGS PARAMETER
UNIT OF
MEASURE
VALUE
DESCRIPTION
DEFAULT
MIN.
MAX.
Time/D
at
e
Hour Format
Hours
12Hr
12Hr
24Hr
Selects 12 or 24 hour time scale.
Time
mm:ss
1:00 AM
1
24
Sets current time. Used for time
stamp in fault log.
Date
MM/DD/
YYYY
1/1/12
–
–
Sets current date. Used for date
stamp in fault log.
PID C
ontr
ol
Proportional
Gain
–
2500
0
10000
Sets the PID controller gain. Used
in conjunction with all
PID Control
parameters to control how fast or
slow the Drive reacts to pressure
changes.
Integration
Time
Milliseconds
500 ms
20 ms 65000
ms
Sets the PID controller integration
time. Used in conjunction with all PID
Control parameters to control how
fast or slow Drive reacts to pressure
changes.
Derivation
Time
Milliseconds
60 ms
0 ms
10000
ms
Sets PID controller derivation time.
Used in conjunction with all PID
Control parameters to control how
fast or slow Drive reacts to pressure
changes.
Derivative
Limit
–
120
0
2000 Sets derivative filter time constant
for PID controller.
Sleep
Boost
Differential
kPa
21 kPa
21 kPa 69 kPa
First part of
Boost Process. Pressure
boost that happens before it goes to
Wake Delay.
Boost Delay
MM:SS
1 Min
30 Sec
5 Min
The time Drive takes to start
Boost
Process after system has stabilized.
Wake Up
Differential
kPa
34 kPa
34 kPa
103
kPa
Pressure amount below setpoint that
wakes up Drive.
Wake Delay
MM:SS
15 Sec
3 Sec
2 Min
Second part of the
Boost Process.
The time it takes to ramp down
pressure during the
Boost Process.
Pa
ss
w
or
d
Password
Time Out
HrHr:mm
1 Hr
1 Min
6 Hr
Amount of time it takes to lock
keypad (after last button is pressed).
Password
–
7777
0000
9999
Password used to unlock keypad.
TABLE 9 - MAIN MENU AND PARAMETERS
Table 9 lists all available commands and parameters for the PENTEK INTELLIDRIVE.
6569 0512
Press PSI Preset
Use arrows to
change the value
Press Enter to Save
Press Enter
Figure 14 - Change PSI Setpoint using
PSI Preset.
6568 0512
Press Auto Start
Use arrows to
change the value
Press Enter to Save
Press Enter
Verify
“Running Fixed Press”
displayed on screen
Figure 13 - Change PSI Setpoint while running
pump.
Keypad Lock - Password
The password locks or unlocks the blue
buttons on keypad. All PENTEK INTELLIDRIVE
units are shipped from factory with the default
password 7777. It can be changed to any other
1 to 4 digit number. To reset password to a
unique password for unit, unlock keypad (see
below) and follow the keypress sequence
shown in Figure 8 to make the change.
If installer does not press the password button,
then the keypad will automatically lock 60
minutes after the Drive is powered up. The
time out period is adjustable (see Table 9).
To unlock keypad press
Password,
use
directional arrows to select numeric code and
press
ENTER.
NOTICE
For more detailed information on
keypad functions, see Figure 2.
Pump Out Operation
Press
Pump Out.
The Drive will start pump in
a constant speed mode (default 45 Hz). The
pump will run until
STOP
or
Auto Start
are
pushed.
Setting the Pressure
NOTICE
Default pressure setting is 414 kPa.
If this value is changed, adjust tank pressure
accordingly (see Table 7).
There are three ways to change the pressure
setpoint:
• While running the pump
Follow keypress sequence shown in Figure
13 to make desired change. This parameter
allows either Internal or External Setpoint to be
changed, depending on which one is referenced
at the time the change is made.
• Via the
PSI Preset
Follow keypress sequence shown in Figure 14 to
make desired change.
• Via the
Main Menu
(Main Menu/Settings/Set
point/Internal Setpoint)
PENTEK IntelliDrive
™
Owner’s Manual
PENTEK IntelliDrive
™
Owner’s Manual
13