background image

PROGRAMMING

PROGRAMMING

MENU 

SETTINGS PARAMETER

UNIT OF 

MEASURE

VALUE

DESCRIPTION

DEFAULT

MIN.

MAX.

Time/D

at

e

Hour Format

Hours

12Hr

12Hr

24Hr

Selects 12 or 24 hour time scale.

Time

mm:ss

1:00 AM

1

24

Sets current time. Used for time 

stamp in fault log.

Date

MM/DD/

YYYY

1/1/12

Sets current date. Used for date 

stamp in fault log.

PID C

ontr

ol

Proportional 

Gain

2500

0

10000

Sets the PID controller gain. Used 

in conjunction with all 

PID Control 

parameters to control how fast or 

slow the Drive reacts to pressure 

changes.

Integration 

Time

Milliseconds

500 ms

20 ms 65000 

ms

Sets the PID controller integration 

time. Used in conjunction with all PID 

Control parameters to control how 

fast or slow Drive reacts to pressure 

changes.

Derivation 

Time

Milliseconds

60 ms

0 ms

10000 

ms

Sets PID controller derivation time. 

Used in conjunction with all PID 

Control parameters to control how 

fast or slow Drive reacts to pressure 

changes.

Derivative 

Limit

120

0

2000 Sets derivative filter time constant 

for PID controller.

Sleep

Boost 

Differential

kPa

21 kPa

21 kPa 69 kPa

First part of 

Boost Process. Pressure 

boost that happens before it goes to 

Wake Delay.

Boost Delay

MM:SS

1 Min

30 Sec

5 Min

The time Drive takes to start 

Boost 

Process after system has stabilized.

Wake Up 

Differential 

kPa

34 kPa

34 kPa

103 

kPa

Pressure amount below setpoint that 

wakes up Drive.

Wake Delay

MM:SS

15 Sec

3 Sec

2 Min

Second part of the 

Boost Process. 

The time it takes to ramp down 

pressure during the 

Boost Process.

Pa

ss

w

or

d

Password 

Time Out

HrHr:mm

1 Hr

1 Min

6 Hr

Amount of time it takes to lock 

keypad (after last button is pressed).

Password

7777

0000

9999

Password used to unlock keypad.

TABLE 9 - MAIN MENU AND PARAMETERS

  

Table 9 lists all available commands and parameters for the PENTEK INTELLIDRIVE.

6569 0512

Press PSI Preset

Use arrows to

change the value

Press Enter to Save

Press Enter

Figure 14 - Change PSI Setpoint using 
PSI Preset.

6568 0512

Press Auto Start

Use arrows to

change the value

Press Enter to Save

Press Enter

Verify

“Running Fixed Press”

displayed on screen

Figure 13 - Change PSI Setpoint while running 
pump.

Keypad Lock - Password

The password locks or unlocks the blue 
buttons on keypad. All PENTEK INTELLIDRIVE 
units are shipped from factory with the default 
password 7777. It can be changed to any other 
1 to 4 digit number. To reset password to a 
unique password for unit, unlock keypad (see 
below) and follow the keypress sequence 
shown in Figure 8 to make the change.
If installer does not press the password button, 
then the keypad will automatically lock 60 
minutes after the Drive is powered up. The 
time out period is adjustable (see Table 9).
To unlock keypad press 

Password,

 use 

directional arrows to select numeric code and 
press 

ENTER.

NOTICE

 For more detailed information on 

keypad functions, see Figure 2.
Pump Out Operation
Press 

Pump Out.

 The Drive will start pump in 

a constant speed mode (default 45 Hz). The 
pump will run until 

STOP

 or 

Auto Start

 are 

pushed.

Setting the Pressure
NOTICE

 Default pressure setting is 414 kPa. 

If this value is changed, adjust tank pressure 
accordingly (see Table 7). 
 

There are three ways to change the pressure 
setpoint: 

• While running the pump

Follow keypress sequence shown in Figure 
13 to make desired change. This parameter 
allows either Internal or External Setpoint to be 
changed, depending on which one is referenced 
at the time the change is made.

• Via the 

PSI Preset

Follow keypress sequence shown in Figure 14 to 
make desired change.

• Via the 

Main Menu

 (Main Menu/Settings/Set 

point/Internal Setpoint)

PENTEK IntelliDrive

 Owner’s Manual

PENTEK IntelliDrive

 Owner’s Manual

13

12

Summary of Contents for PENTEK INTELLIDRIVE PID2000-1123

Page 1: ...SSURE CONTROLLER Should the installer or owner be unfamiliar with the correct installation and or operation of this type of equipment please contact the distributor or manufacturer for the correct advice before proceeding with the installation or operation of this product ...

Page 2: ...age 6 for circuit breaker sizing with no other appliances on the circuit Risk of burns The drive can become hot during normal operation Allow it to cool for 10 minutes after shut down before handling it to avoid burns Risk of electric shock A means for disconnection from the supply mains having a contact separation in all poles must be incorporated in the fixed wiring in accordance with the wiring...

Page 3: ...gnal The Drive senses and processes the signal in the PID Proportional Integration Derivative control When operating in AUTOSTART mode the Drive increases and decreases the speed of the pump motor as needed to maintain constant pressure in the piping system Keypad The keypad programs the Drive monitors the status of the pump and displays faults if they occur Each button has a unique function as de...

Page 4: ...984M 5 5 28 1 33 55 88 Mounting the Drive To mount the Drive as shown in Figure 6 follow this procedure 1 First remove the cover by backing out screw at bottom of front cover 2 Push on backplate with thumbs while pulling the cover toward you with index fingers creating a gap See Figures 3 and 4 3 Pull bottom of cover towards you lift up on cover and remove See Figure 5 Gap Figure 3 Separate cover ...

Page 5: ...ly accepts 230V single phase input power If incoming power does not match this have a qualified electrician alter supply voltage to 230V 1Ph before connecting it to the Drive Terminal Removable pull down 01 01 I1 I1 I2 I2 V V AI AI P N SD CARD Transducer Cable Connections Submersible Motor 3 Ph 3 W 1 Ph follow colors as above Submersible Motor 1 Ph 2 W connect to Y and B any order Above Ground Mot...

Page 6: ... installed before operating the PENTEK INTELLIDRIVE Most installations will only require the initial startup settings However the installer may need to set additional parameters Information about accessing all parameters explanations of their functions and procedures for changing parameter values will be found later in this section 1 Program the Drive Apply power to the PENTEK INTELLIDRIVE Setup G...

Page 7: ...9 lists all available commands and parameters for the PENTEK INTELLIDRIVE 6569 0512 Press PSI Preset Use arrows to change the value Press Enter to Save Press Enter Figure 14 Change PSI Setpoint using PSI Preset 6568 0512 Press Auto Start Use arrows to change the value Press Enter to Save Press Enter Verify Running Fixed Press displayed on screen Figure 13 Change PSI Setpoint while running pump Key...

Page 8: ...VALUE DESCRIPTION DEFAULT MIN MAX Ex Runtime Excessive Runtime Detection _ Enabled Disabled Enabled Enables or disables Excessive Runtime Detection Excessive Runtime Hours Hours 24 1 100 Number of hours Drive can run before it faults on Excessive Runtime Dry Run Auto Restart Delay Minutes 10 Min 3 Min 60 Min Time Drive waits to restart pump when Dry Run is detected Number of Resets 3 0 5 Number of...

Page 9: ...and 8 Amps at up to 230VAC O1 Output relay dry contacts connection Programmed to close when pump is Running or Faulted Positive wires of an external device See Figures 17 and 18 P Positive connection of an RS 485 communication device see Figure 15 Positive wire from RS 485 device Per RS 485 Standard N Negative connection of an RS 485 communication device see Figure 15 Negative wire from RS 485 dev...

Page 10: ...n Possible leak Check for pipe break or large leak Dry running pump Check water level in well Ground Fault Ground wire shorted to motor phase Check the ground wire for short to motor phase wire or check insulation integrity with a megger Long motor cable length If motor cable length is more than 305m a reactor or filter may be needed to limit capacitance between motor wires System Not Grounded Ung...

Page 11: ... Fault Internal voltages are out of range Drive will auto reset and attempt to clear fault Fault Reset can be pressed to clear fault as well Then try to operate pump If fault continues Drive may need replacement Hardware Fault Internal hardware failure Fault Reset can be pressed to clear fault Then try to operate pump If fault continues Drive may need replacement External Fault The external device...

Page 12: ...rial No Dealer Installer Installer Phone No Date of Installation Wire Lengths in Meters Circuit Breaker to Drive PENTEK INTELLIDRIVE to Motor Supply Voltage Note to Installer Record the data listed above for future reference Give manual to end user or attach to PENTEK INTELLIDRIVE when installation is complete OWNER S INFORMATION PENTEK IntelliDrive Owner s Manual 22 ...

Page 13: ...yright law Any reproduction display publication modification or distribution is strictly prohibited without the prior written permission from Pentair Disclaimer Pentair reserves the right to change product specifications and products details All product images are for reference purposes only and may not represent actual and or current product 2022 Pentair All rights reserved ...

Reviews: