PROGRAMMING

PROGRAMMING

MENU 

SETTINGS

PARAMETER

UNIT OF 

MEASURE

VALUE

DESCRIPTION

DEFAULT

MIN

MAX

Se

tpoints

Internal 

Setpoint

kPa

414 kPa

103 kPa

668 kPa 

(Max 

Sensor 

Value 

minus 30 

kPa)

Main pressure setpoint used. 

Sets main system operational 

pressure. This parameter is 

accessed here, through PSI 

Preset button, or by pressing 

Enter button while in Constant 

Pressure operation.

External 

Setpoint

kPa

276 kPa

103 kPa

Max 

Sensor 

Value 

minus 20 

kPa.

Second pressure setpoint. 

When another pressure 

setting is desired other than 

Internal Setpoint. Additional 

programming needed in I/O 

section. Requires an external 

switch or timer to wired to 

I1 or I2 terminals. It is only 

active when there is voltage 

present I1 terminals (see 

Figure 11)  

SUB MENU

PARAMETER

UNIT OF 

MEASURE

DEFAULT

MAX

MIN

DESCRIPTION

Mo

tor

Motor Phase

_

1

3

1

Selects phase of motor to be 

operated. An additional sub 

menu will appear, based on 

phase selection, to select 

proper motor type.

Connection 

Type

3 wire

3 wire

2 wire

Wire type for 1 phase motor 

operation only. Can only access 

by first setting Motor Phase 

parameter to 1 Phase.

Motor Type

Subm

Subm

Above 

Gnd

Motor type for 3 phase, 220V, 

motor operation only. Can only 

access by first setting Motor 

Phase parameter to 3 Phase.

Service Factor 

Amps

A

00.0 A

00.0 A

Per drive 

and 

motor

Service factor amps (max. 

load) of motor the Drive is 

operating. Sets maximum 

allowed amps at output of 

Drive. See Table 7 for values.

Min Frequency

Hz

30 Hz

30 Hz

1 below 

Max Hz

Minimum frequency (speed) 

motor will run.

Max Frequency

Hz

50 Hz

1 above 

Min Hz

 Hz

Maximum frequency (speed) 

motor will run. 

Sensor

Max Sensor 

Value

kPa

689 kPA

2068 kPa

68 kPa

Maximum pressure value of 

transducer sensor used with 

Drive. Only change if different 

transducer is used with Drive, 

other than 689 kPA max scale.

TABLE 9 

(CONTINUED)

TABLE 9 

(CONTINUED)

MENU OR 

SUB MENU

PARAMETER

UNIT OF 

MEASURE

VALUE

DESCRIPTION

DEFAULT

MIN

MAX

Ex Runtime

Excessive 

Runtime 

Detection

_

Enabled

Disabled Enabled Enables or disables Excessive Runtime 

Detection.

Excessive 

Runtime Hours

Hours

24

1

100

Number of hours Drive can run before it 

faults on Excessive Runtime. 

Dr

y Run

Auto Restart 

Delay

Minutes

10 Min

3 Min

60 Min

Time Drive waits to restart pump when 

Dry Run is detected.

Number of 

Resets

3

0

5

Number of tries Drive attempts to 

restart pump when Dry Run condition 

is detected.

Detection Time

M:SS

15 Sec

5 Sec

10 Min

Time the Drive takes to recognize Dry 

Run condition.

Sensitivity

kPa

68 kPA

0

2068 

kPa

Pressure value that Dry Run condition 

is detected at. Dry Run fault will 

occur if this pressure cannot be met 

within Detection Time window. Lower 

pressure = less sensitivity.

Fill Time

M:SS

1 M

15 S

10 M

Time allowed to fill (prime) pipes during 

Auto Line Fill process. Relates to Dry 

Run Sensitivity value. (Time starts after 

55 Hz is reached).

I/O

Digital Input 1

Unused

Selects operation of Drive when 

terminal I1 is used. Select between 

Unused, Run Enabled, Ext Fault, and 

Setpoint. The Drive will respond to 

selected command when voltage is 

present at I1 terminal.

Digital Input 2

Relay Output

Unused

Selects the operation of Drive when 

terminal O1 is used. Select between 

Unused, Run, and Fault. The Drive 

closes the Relay when Run or Fault is 

selected.

Ov

er 

Pr

es

s

Over Pressure

kPa

552 kPa

103 kPa

2047 

kPa

Sets Over Pressure Warning value.  

Change if higher than 552 kPa system 

pressure is needed.

No Gr

ound

No Ground 

Detection

Enabled

Disabled Enabled

Selects whether Ground Detection 

parameter is Enabled or Disabled. If 

Disabled is selected, it will revert back 

to Enabled after 72 hours. Warning LED 

will flash entire time it is Disabled.

Rese

t

Factory Reset

No

No

Yes

Resets all parameters to factory 

defaults. Displays Setup Guide after it is 

complete. Software version displayed 

here. Does not clear fault log.

SW

 

Upda

te

Software 

Update

Disabled

Disabled Enabled Used to update software, if necessary.

PENTEK IntelliDrive

 Owner’s Manual

PENTEK IntelliDrive

 Owner’s Manual

15

14

Summary of Contents for PENTEK INTELLIDRIVE PID2000-1123

Page 1: ...SSURE CONTROLLER Should the installer or owner be unfamiliar with the correct installation and or operation of this type of equipment please contact the distributor or manufacturer for the correct advice before proceeding with the installation or operation of this product ...

Page 2: ...age 6 for circuit breaker sizing with no other appliances on the circuit Risk of burns The drive can become hot during normal operation Allow it to cool for 10 minutes after shut down before handling it to avoid burns Risk of electric shock A means for disconnection from the supply mains having a contact separation in all poles must be incorporated in the fixed wiring in accordance with the wiring...

Page 3: ...gnal The Drive senses and processes the signal in the PID Proportional Integration Derivative control When operating in AUTOSTART mode the Drive increases and decreases the speed of the pump motor as needed to maintain constant pressure in the piping system Keypad The keypad programs the Drive monitors the status of the pump and displays faults if they occur Each button has a unique function as de...

Page 4: ...984M 5 5 28 1 33 55 88 Mounting the Drive To mount the Drive as shown in Figure 6 follow this procedure 1 First remove the cover by backing out screw at bottom of front cover 2 Push on backplate with thumbs while pulling the cover toward you with index fingers creating a gap See Figures 3 and 4 3 Pull bottom of cover towards you lift up on cover and remove See Figure 5 Gap Figure 3 Separate cover ...

Page 5: ...ly accepts 230V single phase input power If incoming power does not match this have a qualified electrician alter supply voltage to 230V 1Ph before connecting it to the Drive Terminal Removable pull down 01 01 I1 I1 I2 I2 V V AI AI P N SD CARD Transducer Cable Connections Submersible Motor 3 Ph 3 W 1 Ph follow colors as above Submersible Motor 1 Ph 2 W connect to Y and B any order Above Ground Mot...

Page 6: ... installed before operating the PENTEK INTELLIDRIVE Most installations will only require the initial startup settings However the installer may need to set additional parameters Information about accessing all parameters explanations of their functions and procedures for changing parameter values will be found later in this section 1 Program the Drive Apply power to the PENTEK INTELLIDRIVE Setup G...

Page 7: ...9 lists all available commands and parameters for the PENTEK INTELLIDRIVE 6569 0512 Press PSI Preset Use arrows to change the value Press Enter to Save Press Enter Figure 14 Change PSI Setpoint using PSI Preset 6568 0512 Press Auto Start Use arrows to change the value Press Enter to Save Press Enter Verify Running Fixed Press displayed on screen Figure 13 Change PSI Setpoint while running pump Key...

Page 8: ...VALUE DESCRIPTION DEFAULT MIN MAX Ex Runtime Excessive Runtime Detection _ Enabled Disabled Enabled Enables or disables Excessive Runtime Detection Excessive Runtime Hours Hours 24 1 100 Number of hours Drive can run before it faults on Excessive Runtime Dry Run Auto Restart Delay Minutes 10 Min 3 Min 60 Min Time Drive waits to restart pump when Dry Run is detected Number of Resets 3 0 5 Number of...

Page 9: ...and 8 Amps at up to 230VAC O1 Output relay dry contacts connection Programmed to close when pump is Running or Faulted Positive wires of an external device See Figures 17 and 18 P Positive connection of an RS 485 communication device see Figure 15 Positive wire from RS 485 device Per RS 485 Standard N Negative connection of an RS 485 communication device see Figure 15 Negative wire from RS 485 dev...

Page 10: ...n Possible leak Check for pipe break or large leak Dry running pump Check water level in well Ground Fault Ground wire shorted to motor phase Check the ground wire for short to motor phase wire or check insulation integrity with a megger Long motor cable length If motor cable length is more than 305m a reactor or filter may be needed to limit capacitance between motor wires System Not Grounded Ung...

Page 11: ... Fault Internal voltages are out of range Drive will auto reset and attempt to clear fault Fault Reset can be pressed to clear fault as well Then try to operate pump If fault continues Drive may need replacement Hardware Fault Internal hardware failure Fault Reset can be pressed to clear fault Then try to operate pump If fault continues Drive may need replacement External Fault The external device...

Page 12: ...rial No Dealer Installer Installer Phone No Date of Installation Wire Lengths in Meters Circuit Breaker to Drive PENTEK INTELLIDRIVE to Motor Supply Voltage Note to Installer Record the data listed above for future reference Give manual to end user or attach to PENTEK INTELLIDRIVE when installation is complete OWNER S INFORMATION PENTEK IntelliDrive Owner s Manual 22 ...

Page 13: ...yright law Any reproduction display publication modification or distribution is strictly prohibited without the prior written permission from Pentair Disclaimer Pentair reserves the right to change product specifications and products details All product images are for reference purposes only and may not represent actual and or current product 2022 Pentair All rights reserved ...

Reviews: