PROGRAMMING
PROGRAMMING
MENU
SETTINGS
PARAMETER
UNIT OF
MEASURE
VALUE
DESCRIPTION
DEFAULT
MIN
MAX
Se
tpoints
Internal
Setpoint
kPa
414 kPa
103 kPa
668 kPa
(Max
Sensor
Value
minus 30
kPa)
Main pressure setpoint used.
Sets main system operational
pressure. This parameter is
accessed here, through PSI
Preset button, or by pressing
Enter button while in Constant
Pressure operation.
External
Setpoint
kPa
276 kPa
103 kPa
Max
Sensor
Value
minus 20
kPa.
Second pressure setpoint.
When another pressure
setting is desired other than
Internal Setpoint. Additional
programming needed in I/O
section. Requires an external
switch or timer to wired to
I1 or I2 terminals. It is only
active when there is voltage
present I1 terminals (see
Figure 11)
SUB MENU
PARAMETER
UNIT OF
MEASURE
DEFAULT
MAX
MIN
DESCRIPTION
Mo
tor
Motor Phase
_
1
3
1
Selects phase of motor to be
operated. An additional sub
menu will appear, based on
phase selection, to select
proper motor type.
Connection
Type
–
3 wire
3 wire
2 wire
Wire type for 1 phase motor
operation only. Can only access
by first setting Motor Phase
parameter to 1 Phase.
Motor Type
–
Subm
Subm
Above
Gnd
Motor type for 3 phase, 220V,
motor operation only. Can only
access by first setting Motor
Phase parameter to 3 Phase.
Service Factor
Amps
A
00.0 A
00.0 A
Per drive
and
motor
Service factor amps (max.
load) of motor the Drive is
operating. Sets maximum
allowed amps at output of
Drive. See Table 7 for values.
Min Frequency
Hz
30 Hz
30 Hz
1 below
Max Hz
Minimum frequency (speed)
motor will run.
Max Frequency
Hz
50 Hz
1 above
Min Hz
Hz
Maximum frequency (speed)
motor will run.
Sensor
Max Sensor
Value
kPa
689 kPA
2068 kPa
68 kPa
Maximum pressure value of
transducer sensor used with
Drive. Only change if different
transducer is used with Drive,
other than 689 kPA max scale.
TABLE 9
(CONTINUED)
TABLE 9
(CONTINUED)
MENU OR
SUB MENU
PARAMETER
UNIT OF
MEASURE
VALUE
DESCRIPTION
DEFAULT
MIN
MAX
Ex Runtime
Excessive
Runtime
Detection
_
Enabled
Disabled Enabled Enables or disables Excessive Runtime
Detection.
Excessive
Runtime Hours
Hours
24
1
100
Number of hours Drive can run before it
faults on Excessive Runtime.
Dr
y Run
Auto Restart
Delay
Minutes
10 Min
3 Min
60 Min
Time Drive waits to restart pump when
Dry Run is detected.
Number of
Resets
–
3
0
5
Number of tries Drive attempts to
restart pump when Dry Run condition
is detected.
Detection Time
M:SS
15 Sec
5 Sec
10 Min
Time the Drive takes to recognize Dry
Run condition.
Sensitivity
kPa
68 kPA
0
2068
kPa
Pressure value that Dry Run condition
is detected at. Dry Run fault will
occur if this pressure cannot be met
within Detection Time window. Lower
pressure = less sensitivity.
Fill Time
M:SS
1 M
15 S
10 M
Time allowed to fill (prime) pipes during
Auto Line Fill process. Relates to Dry
Run Sensitivity value. (Time starts after
55 Hz is reached).
I/O
Digital Input 1
–
Unused
–
–
Selects operation of Drive when
terminal I1 is used. Select between
Unused, Run Enabled, Ext Fault, and
Setpoint. The Drive will respond to
selected command when voltage is
present at I1 terminal.
Digital Input 2
Relay Output
–
Unused
–
–
Selects the operation of Drive when
terminal O1 is used. Select between
Unused, Run, and Fault. The Drive
closes the Relay when Run or Fault is
selected.
Ov
er
Pr
es
s
Over Pressure
kPa
552 kPa
103 kPa
2047
kPa
Sets Over Pressure Warning value.
Change if higher than 552 kPa system
pressure is needed.
No Gr
ound
No Ground
Detection
–
Enabled
Disabled Enabled
Selects whether Ground Detection
parameter is Enabled or Disabled. If
Disabled is selected, it will revert back
to Enabled after 72 hours. Warning LED
will flash entire time it is Disabled.
Rese
t
Factory Reset
–
No
No
Yes
Resets all parameters to factory
defaults. Displays Setup Guide after it is
complete. Software version displayed
here. Does not clear fault log.
SW
Upda
te
Software
Update
–
Disabled
Disabled Enabled Used to update software, if necessary.
PENTEK IntelliDrive
™
Owner’s Manual
PENTEK IntelliDrive
™
Owner’s Manual
15
14