MAINTENANCE INSTRUCTIONS
71
Pressures in excess of 14”WC may damage the internal components of this boiler. Pensotti
REQUIRES
replacment of
the gas valve if it is subjected to pressures in excess of 14”WC. Faliure to comply could cause dangerous operating
conditions, fire, explosion, bodily injury or possible death.
ERROR
CODE
PROBLEM
POSSIBLE CAUSE
REMEDY
RESET
E21
GENERAL PCB
MALFUNCTION
y.
MICROPROCESSOR
MALFUNCTION: IT
DETECTS A WRONG
SIGNAL .
u.
THE PCB RESETS THE ERROR
AUTOMATICALLY
Automatic
E22
PARAMETER
PROGRAMMING
REQUEST
w.
LOSS OF
MICROPROCESSOR
MEMORY.
w.
REPROGRAM PARAMETERS.
Manual Reset
(Switch off the
power supply)
E35
FLAME DETECTION
MALFUNCTION
x.
IONISATION ELECTRODE
MALFUNCTION
y.
IONISATION ELECTRODE
CABLE MALFUNCTION
z.
PRINTED CIRCUIT BOARD
MALFUNCTION
x.
REPLACE OR CLEAN PART
y.
REPLACE PART
z.
REPLACE PART
Manual Reset
(press the ‘
’
Reset button)
E40
ELECTRIC POWER
SUPPLY
aa.
ELECTRIC POWER
SUPPLY OUT OF THE
OPE
RATION RANGE (≤95
/≥130 volts)
aa.
CHECK THE POWER SUPPLY
NETWORK (THE ERROR
DISAPPEARS AUTOMATICALLY
WHEN THE POWER SUPPLY IS
BACK WITHIN THE REQUIRED
RANGE)
Automatic
Burner Electrode & Ionization Specifications
Summary of Contents for PNCC-32N
Page 8: ...GENERAL INFORMATION 5 ...
Page 9: ...GENERAL INFORMATION 6 ...
Page 10: ...GENERAL INFORMATION 7 ...
Page 11: ...GENERAL INFORMATION 8 ...
Page 14: ...INSTALLATION INSTRUCTIONS 11 2 2 Dimensions ...
Page 15: ...INSTALLATION INSTRUCTIONS 12 2 3 Internal parts of the boiler ...
Page 16: ...INSTALLATION INSTRUCTIONS 13 2 5 Water circuit ...
Page 17: ...INSTALLATION INSTRUCTIONS 14 2 5 Circulation pump head flow graph ...
Page 35: ...INSTALLATION INSTRUCTIONS 32 ...
Page 41: ...INSTALLATION INSTRUCTIONS 38 36 ...
Page 43: ...INSTALLATION INSTRUCTIONS 40 ...
Page 45: ...INSTALLATION INSTRUCTIONS 42 ...
Page 76: ...MAINTENANCE INSTRUCTIONS 73 6 10 Exploded Drawings ...
Page 77: ...MAINTENANCE INSTRUCTIONS 74 ...
Page 78: ...MAINTENANCE INSTRUCTIONS 75 ...
Page 79: ...MAINTENANCE INSTRUCTIONS 76 ...