INSTALLATION INSTRUCTIONS
54
5.3 Setting the parameters
P
ARAMETER
P00
–
SELECTS THE TYPE OF BOILER
To enter the parameters menu, follow the previously described procedure (
see
paragraph
5.2 ‘Accessing the parameters menu’
- steps 1-5).
6.
Use ‘
’ and ‘
’
buttons (D.H.W temperature setting)
to modify the
value of the parameter:
00 = NA
01 = PNCC
02 = PNCH with Indirect Water Heater
03 = NA
04 = NA
05 = PNCH
–
NO
Indirect Water Heater
7.
Press mode selection button
‘
’ to confirm and to render the new
adjustment operative. The parameter number (P00) will appear on the
display.
8.
To exit from the parameters menu, press simultaneously ‘
’ and ‘
’
buttons.
P
ARAMETER
P01
-
S
ELECTS THE TYPE OF GAS SUPPLY
To enter the parameters menu, follow the previously described procedure (
see
paragraph
5.2 ‘Accessing the parameters menu’
- steps 1-5).
6.
Use ‘
’ and ‘
’ buttons (D.H.W temperature setting)
to modify the
value of the parameter
00 = Natural Gas
01 = LPG
7.
Press mode selection button ‘
’ to confirm and to render the new
adjustment operative. The parameter number (P01) will appear on the
display.
8.
To exit from the parameters menu, press simultaneously ‘
’ and ‘
’
buttons.
P
ARAMETER
P02
-
S
ETS THE CENTRAL HEATING TEMPERATURE
To enter the parameters menu, follow the previously described procedure (
see
paragraph
5.2 ‘Accessing the parameters menu’
- steps 1-5).
6.
Use ‘
’ and ‘
’ buttons (D.H.W temperature setting)
to modify the
value of the parameter:
00 = standard (86-185°F)
01 = reduced (77-113°F) for under-floor heating
7.
Press mode selection button ‘
’ to confirm and to render the new
adjustment operative. The parameter number (P02) will appear on the
display.
8.
To exit from the parameters menu, press simultaneously ‘
’ and ‘
’
buttons.
P00
03
P00
01
00
P01
01
P01
00
P02
01
P02
Summary of Contents for PNCC-32N
Page 8: ...GENERAL INFORMATION 5 ...
Page 9: ...GENERAL INFORMATION 6 ...
Page 10: ...GENERAL INFORMATION 7 ...
Page 11: ...GENERAL INFORMATION 8 ...
Page 14: ...INSTALLATION INSTRUCTIONS 11 2 2 Dimensions ...
Page 15: ...INSTALLATION INSTRUCTIONS 12 2 3 Internal parts of the boiler ...
Page 16: ...INSTALLATION INSTRUCTIONS 13 2 5 Water circuit ...
Page 17: ...INSTALLATION INSTRUCTIONS 14 2 5 Circulation pump head flow graph ...
Page 35: ...INSTALLATION INSTRUCTIONS 32 ...
Page 41: ...INSTALLATION INSTRUCTIONS 38 36 ...
Page 43: ...INSTALLATION INSTRUCTIONS 40 ...
Page 45: ...INSTALLATION INSTRUCTIONS 42 ...
Page 76: ...MAINTENANCE INSTRUCTIONS 73 6 10 Exploded Drawings ...
Page 77: ...MAINTENANCE INSTRUCTIONS 74 ...
Page 78: ...MAINTENANCE INSTRUCTIONS 75 ...
Page 79: ...MAINTENANCE INSTRUCTIONS 76 ...