INSTALLATION INSTRUCTIONS
25
3.6 Gas Connection
3.6.1 Gas Piping Guidelines
Pressures in excess of 14”WC may damage the internal components of this boiler. Pensotti
REQUIRES
replacment of the gas valve if it is subjected to pressures in excess of 14”WC. Faliure to comply could cause
dangerous operating conditions, fire, explosion, bodily injury or possible death.
Follow all local codes and/or the most recent edition of the National Fuel Gas Code (ANSI Z223.1/NFPA 54) in
the USA or the Natural Gas and Propane Installation Code in Canada (CAN/CSA B149.1).
The installation and use of flexable appliance connectors is prohibited.
3.6.2 Gas Supply Lines Pressures
The minimum and maximum inlet gas pressures are
Natural Gas Min. 6.00
”WC – Max. 14.00”WC. and
Propane Gas Min. 11.00
”WC – Max. 14.00”WC.
Gas pressures over and above the specified range will result in adverse performance and
dangerous operating conditions; any damage resulting from extreme gas supply pressures will not
be covered by the limited warranty.
Until pressure testing of the main gas supply line is completed, ensure the gas line to the PENSOTTI
Boiler is disconnected to avoid any damage to the boiler.
The appliance and its individual shut off valve must be disconnected from the gas supply piping
system during any pressure testing of that system at test pressures in excess of 0.5 psi (14
”wc).
The appliance must be isolated from the gas supply piping system by closing its individual manual
shut-off valve during any pressure testing of the gas supply system at test pressures equal to or less
then 0.5 psi (14
”wc).
The gas appliance and its gas connections must be leak tested before placing the appliance in
operation. Leaks can be found by using a gas leak detection device or by applying soapy water to
all gas fittings. Should bubbles occur, tighten those connections and re-test.
Always purge the gas line for any debris before connecting to the boiler gas inlet.
Never use an open flame to test for gas leaks as property damage, personal injury or death could result.
The maximum inlet gas pressure must not exceed 14
”wc
The connection to the gas supply must be carried out by professionally qualified personnel in accordance with
the relevant standards.
■
Check the internal and external seals of the gas supply system.
■ A gas shut-off valve and sediment trap must be installed upstream of the appliance .
■ Before starting up the boiler, make sure that the type of gas corresponds to that for which the appliance has
been set-up.
■ The gas supply pressure must be between the values reported on
the rating plate.
■ Conversion of the appliance from natural gas to LPG or vice
versa must be carried out by qualified personnel.
■ The power supply cable must be replaced by a qualified
electrician. If the cable is damaged in any way, switch off the
appliance and have the cable replaced by a suitably qualified
electrician.
When using an electrical appliance, a few fundamental rules
must be observed:
Do not touch the appliance with damp or
wet parts of the body or when barefoot. Do not pull on the
electric wires.
Do not allow the appliance to be used by children or anyone
unfamiliar with its operation.
Summary of Contents for PNCC-32N
Page 8: ...GENERAL INFORMATION 5 ...
Page 9: ...GENERAL INFORMATION 6 ...
Page 10: ...GENERAL INFORMATION 7 ...
Page 11: ...GENERAL INFORMATION 8 ...
Page 14: ...INSTALLATION INSTRUCTIONS 11 2 2 Dimensions ...
Page 15: ...INSTALLATION INSTRUCTIONS 12 2 3 Internal parts of the boiler ...
Page 16: ...INSTALLATION INSTRUCTIONS 13 2 5 Water circuit ...
Page 17: ...INSTALLATION INSTRUCTIONS 14 2 5 Circulation pump head flow graph ...
Page 35: ...INSTALLATION INSTRUCTIONS 32 ...
Page 41: ...INSTALLATION INSTRUCTIONS 38 36 ...
Page 43: ...INSTALLATION INSTRUCTIONS 40 ...
Page 45: ...INSTALLATION INSTRUCTIONS 42 ...
Page 76: ...MAINTENANCE INSTRUCTIONS 73 6 10 Exploded Drawings ...
Page 77: ...MAINTENANCE INSTRUCTIONS 74 ...
Page 78: ...MAINTENANCE INSTRUCTIONS 75 ...
Page 79: ...MAINTENANCE INSTRUCTIONS 76 ...