INSTALLATION INSTRUCTIONS
50
4.4 Starting up the boiler
– Requires a Gas Manometer & Electronic Combustion
Analyzer
Once the system has been filled, purged of air, the gas
line
checked for leaks and venting system inspected proceed
as
follows:
Check that the exhaust duct is free from obstructions
and correctly connected to the flue exhaust system.
R
emove the front panel (see 6.3 ‘Accessing the
boiler’);
Loosen the screw of the gas pressure point no. 3 (fig.
1), and insert a Gas Manometer
Switch on the power supply to the boiler;
Open the gas feed valve;
Use button
to select the HEATING ONLY
mode. The symbol
will light up (solid light) to
indicate the selected operation mode;
Turn on all available heating zones. The closure of the
room thermostat(s) contact will then light the burner.
symbol will begin to blink.
In case of flame failure, the ignition system repeats
the ignition procedure after the fan-overrun cycle (20
sec). It may be necessary to repeat the operation in
order to remove all the air from the pipes. To repeat
the operation, wait approximately 15 seconds from
the last ignition attempt before resetting the error
code
E01
(by pressing the reset button
‘
’);
To check the inlet gas pressure value allow the boiler
to
fire;
Press and hold the (reset button)
for several seconds until “F07” appears on the screen (indicating high fire mode);
Observe inlet gas pressure on the manometer. Adjust inlet pressure (6-
7” wc Natural Gas or 11” wc LPG) if necessary
at the gas supply service regulator;
Turn boiler off using the
button so that only the
symbol is displayed.
Close the gas feed valve and remove the gas manometer. Tighten the screw of the pressure port no. 3.
Checking Maximum and Minimum fire gas pressure values.
Check Maximum and Minimum gas pressure setting values. Make sure they comply with those stated on the Gas Data
Table below;
Gas Data Table
NATURAL GAS
LIQUID PROPANE GAS
Boiler Fan Speed
min
max
min
max
Gas Pressure
Inches WC
1.74
4
4.04
10.2
Fig. 1
KEY:
1.
MODULATOR
2.
GAS PRESSURE POINT - OUTLET
3.
GAS PRESSURE POINT
– INLET
Summary of Contents for PNCC-32N
Page 8: ...GENERAL INFORMATION 5 ...
Page 9: ...GENERAL INFORMATION 6 ...
Page 10: ...GENERAL INFORMATION 7 ...
Page 11: ...GENERAL INFORMATION 8 ...
Page 14: ...INSTALLATION INSTRUCTIONS 11 2 2 Dimensions ...
Page 15: ...INSTALLATION INSTRUCTIONS 12 2 3 Internal parts of the boiler ...
Page 16: ...INSTALLATION INSTRUCTIONS 13 2 5 Water circuit ...
Page 17: ...INSTALLATION INSTRUCTIONS 14 2 5 Circulation pump head flow graph ...
Page 35: ...INSTALLATION INSTRUCTIONS 32 ...
Page 41: ...INSTALLATION INSTRUCTIONS 38 36 ...
Page 43: ...INSTALLATION INSTRUCTIONS 40 ...
Page 45: ...INSTALLATION INSTRUCTIONS 42 ...
Page 76: ...MAINTENANCE INSTRUCTIONS 73 6 10 Exploded Drawings ...
Page 77: ...MAINTENANCE INSTRUCTIONS 74 ...
Page 78: ...MAINTENANCE INSTRUCTIONS 75 ...
Page 79: ...MAINTENANCE INSTRUCTIONS 76 ...