background image

Penn | TC3203 | Installation Guide Rev. 

A

 | Part No. 24-7664-03892 | Page 1 of 13 | 

January 20, 2022

TC3203 

Defrost Controller European Installation Guide 

Controller for refrigerated cabinets, counters and islands, with energy-saving strategies 

Figure 1: UI 

Figure 2: Dimensions, mm (in.) 

Figure 3: Drilling template, mm (in.) 

Figure 4: Electrical connection 

ENGLISH 

-

Controller for low temperature units

-

Power supply for TC3203N7x: 230 VAC 

-

Cabinet probe and auxiliary probe with a negative temperature coefficient (NTC), 
10 kohm at 25°C 

-

Door switch or multi-purpose input 

-

Cooling or heating operation 

MEASUREMENTS AND INSTALLATION 

For the dimensions and drilling template, see Figure 2 and Figure 3. Fit the controller to a panel 

with the snap-in brackets supplied. 

INSTALLATION PRECAUTIONS 
-

Ensure that the thickness of the panel is between 0.8 mm and 2.0 mm (1/32 in. and 
1/16 in.) 

-

Ensure that the working conditions are within the limits stated in the 

TECHNICAL 

SPECIFICATIONS

 section. 

-

Do not install the device close to heat sources, equipment with a strong magnetic field, 
in places subject to direct sunlight, rain, damp, excessive dust, mechanical vibrations or 
shocks. 

-

In compliance with safety regulations, install the device correctly to ensure adequate 
protection from contact with electrical parts. Fix all protective parts in such a way so as 
to need the aid of a tool to remove them. 

ELECTRICAL CONNECTION 

Important 

-

Use cables of an adequate wire gauge for the current running through them. 

-

To reduce any electromagnetic interference, connect the power cables as far away 
as possible from the signal cables. 

For the electrical connection diagram, see Figure 4. 

Electrical connection diagram callouts 

Callout 

Description 

Note: 

Maximum 12 A 

Evaporator fans 

Compressor 

Defrost 

Door switch or multi-purpose 

Cabinet 

Auxiliary, configurable 

Power supply for TC3203N7x: 230 VAC 

PRECAUTIONS FOR ELECTRICAL CONNECTION 

-

If you use an electrical or pneumatic screwdriver, adjust the torque to a maximum of 
0.5 

N•m

 (4 in. lb). 

-

If you move the device from a cold to a warm place, the humidity may cause 
condensation to form inside. Wait an hour before you switch on the power. 

-

Make sure that the supply voltage, electrical frequency, and power are within the set 
limits. See 

TECHNICAL SPECIFICATIONS

.

 

-

Disconnect the power supply before you do any type of maintenance. 

-

Do not use the device as safety device. 

-

For repairs and further information, contact the Penn sales network.

FIRST-TIME 

1. 

Follow the instructions in MEASUREMENTS AND INSTALLATION to install the controller.

2. 

Power up the device as shown in 

ELECTRICAL CONNECTION

 and an internal test runs.

The test normally takes a few seconds. When it finishes the display switches off. 

3. 

Configure the device as shown in Table 6.1 in 

SETTINGS.

 

For recommended configuration parameters for first-time use, see the following table. 

PAR.  DEF.  PARAMETER 

MIN. - MAX. 

SP 

0.0 

Setpoint 

r1 to r2 

P2 

Temperature unit of measurement 

0  =  °C 

1  = °F 

d1 

Defrost type 

0  =  Electric  1  = Hot gas 
2  =  Compressor stopped 

Check that the remaining settings are appropriate; see 

CONFIGURATION PARAMETERS

4. 

Disconnect the device from the mains. 

5. 

Make the electrical connection as shown in 

ELECTRICAL CONNECTION 

without powering 

up the device. 

6. 

Power up the device. 

UI AND MAIN FUNCTIONS 

For a figure of the UI, see Figure 1. 

UI callouts 

Callout 

Description 

Energy saving 

n/a 

Temperature unit of measurement 

Compressor 

Defrost 

Evaporator fan 

n/a 

n/a 

On or standby 

10 

SET key and keypad lock 

11 

ON/STANDBY key and escape 

12 

DOWN key and additional functions menu 

13 

UP key and defrost 

4.1 

Switching the device on or off 

1. 

If POF = 1, tap the ON/STAND-BY key for 4 s. 

If the device is switched on, the display shows the P5 value, cabinet temperature by default. If 
the display shows an alarm code, see ALARMS. 

LED 

ON 

OFF 

FLASHING 

Compressor on 

Compressor off 

- Compressor protection active
- Setpoint setting active

Defrost active 

-  Defrost delay active 
- Dripping active

Evaporator fan on 

Evaporator fan off 

Evaporator fan stop active 

- Energy saving active
- Low consumption active

°C/°F

  View temperature 

Device off 

Device on 

Device on or off active 

If 30 s elapse and you do not press the keys, the display shows 

the “

Loc

” label and the keypad 

locks automatically. 

4.2 

Unlocking the keypad 

Tap any key for 1 s. The display shows 

the label “

UnL

”.

 

4.3 

Setting the setpoint 

Check that the keypad is not locked. 

1. 

Tap the SET key. 

2. 

Tap the UP or DOWN key within 15 s to set the value within the 
limits r1 and r2. 

3. 

Tap the SET key or do not operate for 15 s. 

4.4 

Activating manual defrost (if r5 = 0, default) 

Check that the keypad is not locked. 

1. 

Tap the UP key for 2 s. 

If P4 = 1 (default), the defrost activates if the evaporator temperature is lower than the d2 
threshold. 

ADDITIONAL FUNCTIONS 

5.1 

Navigating the additional functions menu 

Before you begin, check that the keypad is not locked. 

1. 

To access the additional functions menu, tap the DOWN key for 

4 s. 

2. 

To navigate to a label, tap the UP or DOWN key within 15 s. 

3. 

To select a label, tap the SET key. 

4. 

If you cannot edit the parameter, the value displays. 

If you can edit the parameter, tap the UP or DOWN key to 
navigate to the delete command 

149

5. 

To set the parameter value, tap the SET key. 

6. 

To exit the procedure, tap the ON/STAND-BY key, or do not 

operate the controller for 60 s. 

5.2 

Additional functions menu 

Use the additional functions menu to cycle through the labels in the following table. 

LABEL 

VALUE 

DESCRIPTION 

CH 

View compressor functioning hours in hundreds 

rCH 

Delete compressor functioning hours 

149 

Command to delete compressor functioning hours 

Pb1 

Cabinet temperature

Pb2 

Auxiliary temperature

SETTINGS 

6.1 

Setting configuration parameters 

1. 

Tap the SET key for 4 s. The display shows 

the label “

PA

”.

 

2. 

Tap the SET key. The display shows 

the label “

PAS

”.

 

3. 

Tap the UP or DOWN key within 15 s to set the password. The 
default password is 

"-19"

4. 

Tap the SET key or do not operate for 15 s. The display shows the 

label “

SP

”.

 

5. 

Tap the UP or DOWN key to select a parameter. 

6. 

Tap the SET key. 

7. 

Tap the UP or DOWN key within 15 s to set the value. 

8. 

Tap the SET key or do not operate for 15 s. 

9. 

Tap the SET key for 4 s, or do not operate for 60 s, to exit the 
procedure. 

6.2 

Restoring the default factory settings and storing customized settings as 
default 

Important 

- Check that the factory settings are appropriate; see 

CONFIGURATION PARAMETERS

.

 

- When you store customized settings, you overwrite the default.

1. 

Tap the SET key for 4 s. The display shows 

the label “

PA

”.

 

2. 

Tap the SET key. 

3. 

Tap the UP or DOWN key within 15 s to set the value. 

VAL. 

DESCRIPTION 

149 

Restores the default factory settings 

161 

Stores customized settings as default 

4. 

Tap the SET key or do not operate for 15 s. The display shows the 
label 

dEF

  when  you  set  the  value 

149

  or  the  label 

MAP

” 

when you set the value 

161

”.

 

5. 

Tap the SET key. 

6. 

Tap the UP or DOWN key within 15 s to set 

4

7. 

Tap the SET key or do not operate for 15 s. The display shows   "- 
- -" flashing for 4 s, then the device exits the procedure. 

8. 

Interrupt the power supply to the device. 

9. 

Tap the SET key 2 s before step 6. to exit the procedure 
beforehand. 

ALARMS 

COD.  DESCRIPTION 

RESET 

REMEDIES 

Pr1 

Cabinet probe alarm 

Automatic 

- Check P0 

Pr2 

Auxiliary probe alarm 

Automatic 

- Check probe integrity 
- Check electrical connection 

AL 

Low temperature alarm 

Automatic 

Check A1 

AH 

High temperature alarm 

Automatic 

Check A4 

id 

Open door alarm 

Automatic 

Check i0 and i1 

COH 

High condenser temperature 
warning 

Automatic 

Check C6 

CSd 

High condenser temperature 
alarm 

Manual 

- Switch the device off and on 
- Check C7 

iA 

Multi-purpose input alarm 

Automatic 

Check i0 and i1 

dFd 

Defrost timeout alarm 

Manual 

- Tap any key 
- Check d2, d3 and d11 

ELECTRICAL RATINGS 

Output 

Units 

cULus  (UL 60730) 

CE (EN 60730) 

Applied voltage at 60 Hz 

120 VAC 

240 VAC 

240 VAC 

K1 

compressor 
relay 

Resistive amperes 

12 

12 

12 

Inductive amperes 

 

 

Full load amperes 

10 

10 

 

Locked rotor amperes 

60 

60 

 

K2 relay 

Resistive amperes 

Inductive amperes 

 

 

Full load amperes 

4.4 

2.9 

 

Locked rotor amperes 

26.4 

17.4 

 

K3 

evaporator 

fan relay 

Resistive amperes 

Inductive amperes 

 

 

Full load amperes 

1.5 

1.5 

 

Locked rotor amperes 

 

TECHNICAL SPECIFICATIONS 

Purpose of the control device

Function controller

Construction of the control device

Built-in electronic device

Container 

Black, self-extinguishing 

Category of heat and fire resistance 

Measurements 

75 mm x 33 mm x 59 mm (2 15/16 in. x 1 
5/16 in. x 2 5/16 in.) 

Mounting methods for the control device 

Fit the controller to a panel with the snap-in 
brackets supplied 

Degree of protection provided by the covering  IP65 in front 
Connection method 

Fixed screw terminal blocks for wires up to 

2.5 mm² 

Maximum permitted length for connection cables 
Power supply: 10 m (32.8 ft) 

Analog inputs: 10 m (32.8 ft) 

Digital inputs: 10 m (32.8 ft) 

Digital outputs: 10 m (32.8 ft) 

Operating temperature

From 0°C to 55°C (from 32°F to 131°F)

Storage temperature

From -25°C to 70°C (from -13°F to 158°F)

Operating humidity 

Relative humidity without condensate from 
10% to 90%

Pollution status of the control device 

Compliance 
United States  cURus Recognized; File SA32187 CCN SDFY2; FCC Compliant to CFR47, Part 

15, Subpart B, Class A limits 

Canada 

cURus Recognized; File SA32187 CCN SDFY8; Industry Canada (IC) compliant 

to Canadian ICES-003, Class A limits 

Europe 

Johnson Controls declares that this product is in compliance with the essential 

requirements and other relevant provisions of the EMC Directive, Low Voltage 
Directive, and RoHS Directive 

Power supply 

TC3203N7x 

230 VAC (+10% -15%), 50/60 Hz (+/- 3Hz), max. 2 VA 

Grounding methods for the control device 

None 

Rated impulse-withstand voltage

4 KV 

Over-voltage category

III 

Software class and structure

Analog inputs 

2 for NTC probes (cabinet probe and auxiliary 
probe)

NTC probes 

Sensor type

ß3435 (10 kohm at 25°C, 77°F,) 

Measurement field

-40°C to 105°C (-40°F to 221°F)

Resolution

0.1°C (1°F)

Digital inputs

1 dry contact (door switch/multi-purpose)

Dry contact 

Contact type 

5 VDC, 1.5 mA 

Power supply 

None 

Protection 

None 

Digital outputs 

3 electro-mechanical relays (compressor, defrost and 
evaporator fan) 

Type 1 or Type 2 actions 

Type 1

Additional features of Type 1 or Type 2 
actions

Display

3-digit custom display with function icons 

10 

PRODUCT WARRANTY 

This product is covered by a limited warranty, details of which can be found at 

www.johnsoncontrols.com/buildingswarranty

 

11 

SOFTWARE TERMS 

Use of the software that is in (or constitutes) this product, or access to the cloud, or hosted 
services applicable to this product, if any, is subject to applicable end-user license, open-
source software information, and other terms set forth a

www.johnsoncontrols.com/techterms

Your use of this product constitutes an agreement to such terms. 

12 

SINGLE POINT OF CONTACT 

APAC 

Europe 

NA/SA 

JOHNSON CONTROLS 

C/O CONTROLS PRODUCT 
MANAGEMENT 
NO. 32 CHANGJIJANG RD NEW 

DISTRICT 
WUXI JIANGSU PROVINCE 
214028 
CHINA 

JOHNSON CONTROLS 

WESTENDHOF 3 
45143 ESSEN 
GERMANY 

JOHNSON CONTROLS 

507 E MICHIGAN ST 
MILWAUKEE WI 53202 
USA 

13 

CONTACT INFORMATION 

Contact your local branch office: 

www.johnsoncontrols.com/locations

 

Contact Johnson Controls: 

www.johnsoncontrols.com/contact-us

 

Important 

The device must be disposed of according to local regulations governing the collection 
of electrical and electronic waste. 

This document and the solutions contained therein are the intellectual property of Penn and thus 
protected by the Italian Intellectual Property Rights Code (CPI). Penn imposes an absolute ban on the 
full or partial reproduction and disclosure of the content other than with the express approval of Penn. 
The customer (manufacturer, installer or end-user) assumes all responsibility for the configuration of the 
device. Penn accepts no liability for any possible errors in this document and reserves the right to make 
any changes, at any time without prejudice to the essential functional and safety features of the 
equipment.

 

Summary of Contents for TC3203

Page 1: ...the password The default password is 19 4 Tap the SET key or do not operate for 15 s The display shows the label SP 5 Tap the UP or DOWN key to select a parameter 6 Tap the SET key 7 Tap the UP or DOW...

Page 2: ...und Na displeji se zobraz daj SP 5 Stiskem tla tka NAHORU nebo DOL vyberte parametr 6 Stiskn te tla tko SET NASTAVIT 7 Stiskem tla tka NAHORU nebo DOL do 15 sekund nastavte hodnotu 8 Stiskn te tla tko...

Page 3: ...er etiketten SP 5 Tryk p OP eller NED tasten for at v lge en parameter 6 Tryk p SET INDSTILLINGS tasten 7 Tryk p OP eller NED tasten inden for 15 sek for at indstille v rdien 8 Tryk p SET INDSTILLINGS...

Page 4: ...Taste um das Passwort einzustellen Dieses lautet standardm ig 19 4 Dr cken Sie die SET Taste EINSTELLEN oder bet tigen Sie 15 Sekunden lang nicht die Tastatur Das Display zeigt SP an 5 Dr cken Sie die...

Page 5: ...durante 15 s La pantalla muestra la etiqueta SP 5 Pulse la tecla ARRIBA o ABAJO para seleccionar un par metro 6 Pulse la tecla SET ajustar 7 Pulse la tecla ARRIBA o ABAJO durante 15 s para definir el...

Page 6: ...ran affiche PAS 3 Appuyer sur la touche HAUT ou BAS dans les 15 s pour d finir le mot de passe Le mot de passe par d faut est 19 4 Appuyer sur la touche SET D FINIR ou ne pas modifier le r gulateur pe...

Page 7: ...nita 19 4 Toccare il tasto SET IMPOSTA o non utilizzare per 15 s Sul display compare l etichetta SP 5 Toccare il tasto SU o GI per selezionare un parametro 6 Toccare il tasto SET IMPOSTA 7 Toccare il...

Page 8: ...wachtwoord is 19 4 Tik op de toets SET STEL of gebruik het apparaat 15 seconden niet Het display geeft het label SP weer 5 Tik op de toets OMHOOG of OMLAAG om een parameter te selecteren 6 Tik op de t...

Page 9: ...P eller NED for velge en parameter 6 Klikk p SET Innstilling tasten 7 Trykk p piltasten opp eller ned innen 15 sekunder for stille inn verdien 8 Klikk p SET Innstilling tasten eller ikke bruk den i 15...

Page 10: ...omy lne has o to 19 4 Nacisn klawisz SET USTAW lub nie u ywa przez 15 s Na wy wietlaczu zostanie wy wietlona etykieta SP 5 Nacisn klawisz W G R lub W D aby wybra parametr 6 Nacisn klawisz SET USTAW 7...

Page 11: ...SP 5 Toque na tecla PARA CIMA ou PARA BAIXO para selecionar um par metro 6 Toque na tecla SET DEFINIR 7 Toque na tecla PARA CIMA ou PARA BAIXO dentro de 15 s para definir o valor 8 Toque na tecla SET...

Page 12: ...nin kuluessa 8 Napauta SET ASETA n pp int tai l tee mit n 15 sekunnin ajan 9 Poistu toimenpiteest painamalla SET ASETA n pp int 4 sekunnin ajan tai l tee mit n 60 sekunnin ajan 6 2 Tehdasasetusten pal...

Page 13: ...15 sekunder Sk rmen visar text SP 5 Tryck p UPP eller NED knappen f r att v lja en parameter 6 Tryck p SET ST LL IN knappen 7 Tryck p UPP eller NED knappen inom 15 sek f r att st lla in v rdet 8 Tryck...

Reviews: