Installation
Prerequisites
DK9401A1
www.pelltech.eu
3 Installation
3.1 Prerequisites
In order to install the burner, the boiler must meet to the following requirements:
Recommended to use three pass boilers.
The construction of the boiler must make it possible to open the door of the boiler with the
burner connected and removing ash from the furnace. If the door of the boiler is too narrow for
opening it with the burner, then extra hinges must be installed.
If there is not sufficient (less than 5Pa) negative pressure in the furnace, a draught fan should be
installed for the exhaust gases.
The boiler must be positioned in a way that there is enough space for cleaning the burner, the
boiler, the smoke pipe and removing the ash.
The burning chamber must not touch the bottom of the boilers furnace (min 10cm distance
needed).
The boiler room where the burner is installed must fulfill all rules and recommendations given by
local authorities.
Boiler room must provide constant air supply of 1500 m³ per hour (ca. 1600 cm2 air inlet
opening).
In order to install the burner to the boiler door, there must be
mounting holes as shown below.
Figure 4 Boiler door mounting hole
Note: If the burner is installed to the boiler, the door or the
installation flange´s thickness should be 8-14mm.
Unit
PV 1000
mm
400
mm
490
mm
6x13
deg
30
angle between bolt holes
60
⌀
D
hole for burning chamber neck
⌀
D1
flange bolt ring diameter
⌀
D2
bolt holes
a
bolt hole offset angle
deg
Summary of Contents for PV1000agri
Page 1: ...PV1000agri pellet burner User manual POOLELI DRAFT DK9401A1 ...
Page 24: ...PV1000agri pellet burner p 23 50 Installation Electrical connections DK9401A1 www pelltech eu ...
Page 25: ...PV1000agri pellet burner p 24 50 Installation Electrical connections DK9401A1 www pelltech eu ...
Page 26: ...PV1000agri pellet burner p 25 50 Installation Electrical connections DK9401A1 www pelltech eu ...