PV 100a
Table 6 Parameters menu
Parameter
Description
Unit
Value
Nr
Name
Default Min.
Max.
1
BURN AIR @50kW
Fan speed at power level 1
rps
22
20
24
2
BURN AIR @60kW
Fan speed at power level 2
rps
25
23
27
3
BURN AIR @70kW
Fan speed at power level 3
rps
27
25
29
4
BURN AIR @80kW
Fan speed at power level 4
rps
30
28
32
5
BURN AIR @90kW
Fan speed at power level 5
rps
34
32
36
6
BURN AIR @100kW
Fan speed at power level 6
rps
38
36
40
7
TESTING AIR
Fan speed for testing
rps
42
38
50
8
IGNITION AIR
Fan speed during ignition cycle
rps
25
20
35
9
BURN END AIR
Fan speed durinf end blow cycle
rps
20
10
30
10
HOLD FLAME AIR
Fan speed during hold flame cycle
rps
10
7
14
11
HOLD FLAME ON
In case of Hold flame is set on
AUTO, flame holding activated
after 2 waiting session, both less
then 15 min.
min
15
5
30
12
HOLD FLAME OFF
In case of Hold flame is set on
AUTO, there is maximum time for
flame holding cycle.
min
60
30
90
13
MIN POWER
Minimum power level
kW
70
50
100
14
MAX POWER
Maximum power level
kW
90
50
100
15
AUTO POWER UP
min
60
30
120
16
AUTO POWER DOWN
min
30
15
45
21
PELLET NORMAL
Internal feeder production
g/rot
78
60
100
22
PELLET LIGHT
Internal feeder production
g/rot
72
60
100
23
PELLET HEAVY
Internal feeder production
g/rot
84
60
100
24
LOADING FEED
Feeder turns during loading cycle
rot
21
20
24
25
LOADING 2 FEED
Feeder turns during second
loading cycle
rot
3
1
8
26
BURN END FEED
rot
15
10
20
30
SMOKEFAN ON
Smokefan is turned ON or OFF
OFF
ON/OFF
31
SMOKEFAN 1
Smokegas fan speed for ignition,
end blow, burn at power level 1
and 2
%
40
0
100
32
SMOKEFAN 2
Smokegas fan speed for burn at
power level 3 and 4
%
60
0
100
33
SMOKEFAN 3
Smokegas fan speed for burn at
power level 5 and 6
%
80
0
100
40
PHOTOCELL
Photocell sensitivity
%
84
50
100
41
PREBURN TIME
Preburn cycle lenght
s
50
30
100
42
PREBURN CYCLES
n
2
1
4
43
OVERHEAT TEMP
Maximum allowed burner
°C
50
20
70
25