Rev. 02-19 Page 33
USER MANUAL
dO4
Setting the functions of the digital output dO4.
The less sign indicates the reverse status of the relay.
With the exception of settings 1, -1, 2, -2, the relay is
deactivated in case of no enabling or it is in stand-by.
4 = Relay excited for essence call
3 = Inlet fan relay (activated with steam production request)
2 =
Relay activated when the appliance is in stand-by or for
absence of consent.
1 = Relay activated in presence of an alarm
0 = Relay Disabled
-1 = Relay deactivated in presence of an alarm
-2 = Relay deactivated when the appliance is in stand-by or
for absence of consent.
-3 = Outlet fan relay (deactivated with steam production
request)
-3 ÷ 4
1
1
dO5
Setting the functions of the digital output dO5.
The less sign indicates the reverse status of the relay.
With the exception of settings 1, -1, 2, -2, the relay is
deactivated in case of no enabling or it is in stand-by.
4 = Relay excited for essence call
3 = Inlet fan relay (activated with steam production request)
2 =
Relay activated when the appliance is in stand-by or for
absence of consent.
1 = Relay activated in presence of an alarm
0 = Relay Disabled
-1 = Relay deactivated in presence of an alarm
-2 = Relay deactivated when the appliance is in stand-by or
for absence of consent.
-3 = Outlet fan relay (deactivated with steam production
request)
-3 ÷ 4
3
3
HSE
Maximum value attributable to the setpoint
0 ÷ 99
99
99
BEE
Buzzer enable
0 = disable
1 = enable
1
1
Ad
Network address for connection to the MODBUS-
RTU supervision system or for the master-slave
configuration.
Note: In Master mode, you can assign address 0.
1 ÷ 247
if MS ≤ 1
0 ÷ 247
if MS > 1
1
1
MS
Setting the Master-Slave operating mode.
(with MS=0 the modbus is enabled)
0 = Single
4 = 3 slaves
1 = Slave
5 = 4 slaves
2 = 1 slave
6 = 5 slaves
3 = 2 slaves
0 ÷ 6
0
0