Page 32 Rev. 02-19
USER MANUAL
CA1
Humidity probe calibration
(used when S9 = 1, 3, 5, 6)
-20 % ÷ 20 %
0 %
0 %
CA2
Air duct humidity probe calibration
(used when S9 = 3, 4, 6)
-20 % ÷ 20 %
0 %
0 %
CA3
NTC probe value correction
(used when S9 = 7, 9)
-10.0 ÷ 10.0 °C
0,0
0,0
t1
Delay in seconds to restart the humidifier.
The delay starts from the moment when the humidity in the
air duct, after passing StC, has returned below StC-r0. Only
after this delay the normal functioning will be resumed. (used
when S9 = 3, 4, 6)
0 ÷ 240 s
10 s
10 s
t2
Operating time ON for the essence.
If steam production is in progress and the temperature is
higher than 70% of the SET set point, the configured relay
calls the essence for time t2 and waits for the time t3 between
one call and another. (used only when S9=7)
1 ÷ 30 s
2 s
2 s
t3
Operating time OFF for the essence.
If steam production is in progress and the temperature is
higher than 70% of the SET set point, the configured relay
calls the essence for time t2 and waits for the time t3 between
one call and another. With t3 = 0 there is the continuous call
of the essence, if the above conditions are satisfied. (used only
when S9 = 7, 9)
0 ÷ 99 min
5
min
5 min
t4
Timer for manual insertion of outlet fans.
Function that can be activated manually with the key
combination down arrow + Stand-by and active only with
S9 = 7, 9 and dO4 or dO5 = -3 and humidifier in stand-by.
At the end of the day, once the system is put on stand-by, it is
possible to operate the outlet fans for a certain period to dry
the room.
0 ÷ 24 hours
0 = Disabled
0
0
t5
Activation time for the E9 Serious Alarm.
When the E8 alarm remains permanently for more then a time
t5, the E9 serious alarm is activated.
The E9 alarm is activated even if in a period of 12 hours
occur 3 E8 alarm situations.
The E9 alarm is disabled with t5=0.
0 ÷ 99 min
0 = Disabled
15
min
15
min
t6
Inlet fan activation time.
The relay configured for the inlet fan remains energized for a
time t6 after the steam production has been switched off.
This ensure the extraction of the steam from the cylinder and
prevents the formation of condensation in the eventual fan
unit.
t6 = -1: continuous operation (even in stand-by or alarm)
0 ÷ 60 min
-1 = continuous
operation
20
min
20
min
In1
Setting of the digital input In1 and its activation status.
±10 = drive of the drain pump
±9 = reduced operation to 90%
±8 = reduced operation to 80%
±7 = reduced operation to 70%
±6 = reduced operation to 60%
±5 = reduced operation to 50%
±4 = reduced operation to 40%
±3 = reduced operation to 30%
±2 = Enabling (in series to possible In2 and In3 enabling)
±1 = alarm input
0 = disabled
“+”
for active input with closed contact
“-“ for active input with open contact
-10 ÷ 10
2
2
In2
Setting of the digital input In2 and its activation status.
See In1 options
-10 ÷ 10
10
10
In3
Setting the VOLTAGE input In3 and its activation status.
See In1 options
-10 ÷ 10
0
0