REPLACEMENT OF THE CYLINDER
The only consumable item of the humidifier is the cylinder, when the electrodes are worn
due to functioning or it's not possible to eliminate all the limestone deposit formed within.
The EASYSTEAM series is provided with steel electrodes for longer duration that, however,
depends on the amount of water (level of conductivity and hardness) and work output to which the
humidifier is submitted.
When the electrodes are worn making cylinder replacement necessary, the water level rises
anomalously compared to optimal functioning, repeatedly triggering the maximum level alarm
E1
.
Now having checked the alarm is not caused by other anomalies (see chapter 6 Diagnostics), carry
out replacement as indicated below:
NEVER REPLACE THE CYLINDER WITH THE MACHINE HOT AND WITH
WATER INSIDE. BEFORE PERFORMING THE REPLACING, EMPTY
COMPLETELY THE CYLINDER USING THE MANUAL DISCHARGE KEY!
IT IS COMPULSORY TO FOLLOW THE PRESCRIPTIONS INDICATED IN
CHAPTER 7.2
1.
Open the humidifier extracting the front cover as indicated in chapter 2.2.
2.
Remove the steam tube by loosening the clamping band and pulling it upwards. (Fig.10).
Fig. 10
3.
Remove the rubber plugs above the cylinder and disconnect the cables by unscrewing the nuts
securing the cable lugs (fig. 11). Unhook the O-ring that holds the cylinder fixed to the support
(fig. 12).
Fig. 11 Fig. 12