33
ENGLISH |
DISPLAY
PARAMETERS
DESCRIPTION
u.m. Default Min
Max
Step
RF 4
RAPIDITY OF
INVERTER REACTION
Sets the rapidity of response of the inverter
to changes in pressure; the rapidity of the
responses depends on the characteristics
of the facility.
-
3
1
5
1
FS 10
FREQUENCY OF
COMMUTATION OF
THE MODULE
Sets the frequency of commutation of
the power module. In the case of a long
power cable without a sinusoidal filter
this frequency must be reduced to the
minimum value.
kHz
8
4
12
2
US 0
ANTI-BLOCKAGE
START-UPS
Sets the interval between two successive
automatic “anti-blockage” start-ups (for
long periods of inactivity); setting the
value at “0” the function is disabled.
min
0
0
999
1
EI 0
ENTRANCE SIGNAL
Sets the FUNCTION of the incoming signal
(of the clean contact type , NO or NC)
-
0
Values of the parameter
0/ 1/ 2/ 3/ 4/ 5
El = 0: no function, the state of the entrance is ignored
El = 1: entrance level signal (NC)
El = 2: start and stop by external signal (NC)
El = 3. Passage to the 2nd SETPOINT of pressure (NC)
El = 4: entrance external flow signal (NC): substitutes the signal coming from the
non-return valve
El = 5. Entrance alarm reset signal
EO 0
EXIT SIGNAL
Max 2 A @ 250 Vac
Max 1 A @ 30 Vdc
Sets the FUNCTION of the exit signal (of the
clean contact type, NO or NC)
-
0
Values of the parameter
0/ 1/ 2/ 3
EO = 0: no function; the relay has not been activated
EO = 1: alarm sounds; the relay is activated if the inverter alarm is set off
EO = 2: pump switched on: the relay is activated if the pump is switched on
EO = 3: recycling function; activates the exit relay at time intervals defined by the
Al parameter
AI 60
RECYCLING
FUNCTION (min)
Sets the intervals of activation of the exit
signal (of the clean contact type) and it is
active if E0 is set at value 3
min
60
1
999
1
AT 10
RECYCLING
ACTIVATION TIME
Sets the intervals of activation of the exit
signal (of the clean contact type)
sec
10
1
999
1
W NC
LINE OF INVERTER
Activates the communication between two
or more inverters
defining the task of each unit: MS (MASTER
Unit), S1/S2 (SLAVE units), NC (operation
with a single inverter)
-
NC
Values of the parameter
NC/ MS/ S1/ S2
V 230
LINE VOLTAGE (V)
Defines the supply voltage
230 V for single-phase powered versions
400 V for three-phase powered versions
V
-
-
-
-
Follows
i
Summary of Contents for TISSEL-100
Page 2: ......
Page 77: ...77 30 5 TISSEL 100 TISSEL 100 OFF ON...
Page 80: ...80 30 TISSEL 100 TISSEL 100 10 Qmax 80 V 80 x 10 8 70 Pset 4 4 x 70 2 8 TISSEL 100 230 50...
Page 83: ...83 BASIC P 2P A RO ADV d MF LF HF Td PF TPF TP TF RF FS US EI i...
Page 84: ...84 EO AI AT W V Pd iDRY FM FLAT SET F INSP WH TH NS SH E1 E1H E2 E2H E3 E3H E4 E4H EE TEST...
Page 94: ......
Page 95: ......