28
| ENGLISH
DISPLAY
DESCRIPTION
U.M.
P 3.2
SYSTEM PRESSURE
Measured pressure of the system
bar
F 45
WORK FREQUENCY
Immediate frequency of operation of the motor
Hz
A 6.5
ABSORBED CURRENT
Immediate current absorbed by the motor – ATTENTION: RMS value:
the reading of the electric current entering and exiting from the inverter, registered by normal
measuring instruments (eg. amperometric clamp), could be incorrect.
A
Tm 50
TEMPERATURE OF POWER MODULE
Temperature of the electronic power module of the inverter
°C
VISUALISATION OF THE FIRMWARE VERSION (FW)
In order to visualise the FIRMWARE (FW) version of the INTERFACE (FWI) card and the POWER (FWP) card:
• Take the TISSEL-100 OUT OF SERVICE (OFF) by pressing the
key
• Press both the keys at the same time
SETTING THE PARAMETERS IN THE HIDDEN LISTS
In order to enter into the HIDDEN LISTS where there are the advanced parameters and if it were necessary to modify the factory
values of these same parameters proceed as follows.
• Take the TISSEL-100 OUT OF SERVICE (OFF) by pressing the
key
• Press both the keys at the same time
+
+
HIDDEN LISTS
BASIC
BASIC LIST
Parameters
These are BASIC PARAMETERS which have to be set depending on the
application.
ADV
ADVANCED LIST
Parameters
These are the ADVANCED PARAMETERS which improve the functioning and which
require a detailed knowledge of the system.
INSP
INSPECTION LIST
Parameters
These are the INSPECTION PARAMETERS which enable the user to inspect the
operational status of the system, visualising hours of work, number of starts,
history of the alarms, etc.
TEST
TEST Mode
(accessible only in the OFF
mode)
The TEST mode allows one to start and stop the pump manually (ON/OFF key)
and modify the frequency by 1 Hz at a time. It also allows one to control the
functional parameters of the motor and of the inverter.
ATTENTION: when functioning manually some of the automatic
controls are excluded and the operator must avoid any wrong
manoeuvres.
Summary of Contents for TISSEL-100
Page 2: ......
Page 77: ...77 30 5 TISSEL 100 TISSEL 100 OFF ON...
Page 80: ...80 30 TISSEL 100 TISSEL 100 10 Qmax 80 V 80 x 10 8 70 Pset 4 4 x 70 2 8 TISSEL 100 230 50...
Page 83: ...83 BASIC P 2P A RO ADV d MF LF HF Td PF TPF TP TF RF FS US EI i...
Page 84: ...84 EO AI AT W V Pd iDRY FM FLAT SET F INSP WH TH NS SH E1 E1H E2 E2H E3 E3H E4 E4H EE TEST...
Page 94: ......
Page 95: ......