49
8 - INSTALLATION - Vent & combustion air
Figure 36 - Concentric sidewall multiple boilers
terminations
CAUTION!!! DO NOT use fi eld-
supplied couplings to extend pipes.
Airfl ow restriction will occur and may
cause intermittent operation.
6. Operate the appliance one (1) heat
cycle to ensure combustion air and
vent pipes are properly connected
to the concentric vent termination
connections.
8.11.3 - Multiventing
sidewall terminations
When two or more direct vent
appliances are vented near each
other, each appliance must be
individually vented and vent
terminations may be installed as
shown in Figure 36. It is important that
vent terminations be made as shown
to avoid recirculation of fl ue gas.
WARNING!!! Do not connect
any other appliance to the vent pipe
or multiple boilers to a common vent
pipe. Failure to comply could result
in severe personal injury, death, or
substantial property damage.