4. use the precedent clamp “D” to
mechanically secure the adapter
“E” to the adapter “A”. To do this
tighten the half clamp on the
adapter “A” and half clamp on the
adapter “E”. Tight the clamps with
a tork of 1.5 - 2 lbf ft (2-3 Nm).
5. insert the clamp “F” into convertor
“E”.
6. insert the air inlet PVC/CPVC
pipe, for 2” into the adapter “E”;
7. use the precedent clamp “F” to
mechanically secure the pipe to
the adapter “E”. To do this tighten
the half clamp on the pipe and half
clamp to the adapter “E”. Tight the
clamps with a tork of 1.5 - 2 lbf ft
(2-3 Nm).
Vent connection (see Figure
29 Item “B”).
This connection is used to provide
a passageway for conveying
combustion gas to the outside. Vent
piping must be supported per the
National Building Code, Section 305,
Table 305.4 or as local codes dictate.
To connect a PVC/CPVC pipe to the
vent connection proceed as follow
while referring to Figure 29:
1. install boiler adapter “A” above
boiler. Rotate boiler adapter “A” so
as air intake and vent connections
are in the desired left or right
side. Check stamped arrow to
understand which is the vent and
air intake connection.
WARNING!!! Check stamped
arrow on boiler adapter for the
correct side of vent. Failure to follow
this warning could result in excessive
levels of carbon monoxide or a fi re,
which can result in severe personal
injury or death!
2. Insert one side of clamp “D” onto
the air intake of boiler adapter “A”
(side C).
3. Insert adapter “E” into side “C” of
boiler adapter “A”;
4. Use clamp “D” to mechanically
secure adapter “E” to boiler
adapter “A”. To do this, tighten
one side of clamp “D” onto boiler
adapter “A” and the other half of
clamp “D” onto adapter “E”. Tight
the clamps with a tork of 1.5 - 2 lbf
ft (2-3 Nm).
5. Insert clamp “F” into adapter “E”.
6. Insert the PVC/CPVC pipe “G”,
into adapter “E” for at least 2”;
7. Use clamp “F” to mechanically
secure pipe “G” to adapter “E”. To
do this, tighten one side of clamp
“F” onto pipe “G” and the other
side of clamp “F” to the adapter
“E”. Tight the clamps with a tork of
1.5 - 2 lbf ft (2-3 Nm).
WARNING!!! Check stamped
arrow on boiler adapter for the correct
side of fl ue exhaust and air intake.
Failure to follow this warning could
result in excessive levels of carbon
monoxide or a fi re, which can result
in severe personal injury or death!
WARNING!!! Do not insulate
PVC/CPVC exhaust pipe nor install
into an enclosure, closet, alcove
or any other obstruction thereby
preventing the cooling of the exhaust
pipe. Failure to follow this warning
could result in excessive levels of
carbon monoxide or a fi re, which can
result in severe personal injury or
death!
Figure 29 - PVC/CPVC Venting connection
8 - INSTALLATION - Vent & combustion air