3
2. Required Combustion Air Volume: The total
required volume of indoor air is to be the sum of the
required volumes for all appliances located within
the space. Rooms communicating directly with the
space in which the appliances are installed and
through combustion air openings sized as indicated
in Subsection 3 are considered part of the required
volume. The required volume of indoor air is to be
determined by one of two methods.
a.
Standard Method:
The minimum required
volume of indoor air (room volume) shall be 50
cubic feet per 1000 BTU/Hr (4.8 m
3
/kW). This
method is to be used if the air infiltration rate is
unknown or if the rate of air infiltration is known
to be greater than 0.6 air changes per hour. As
an option, this method may be used if the air
infiltration rate is known to be between 0.6 and
0.4 air changes per hour. If the air infiltration
rate is known to be below 0.4 then the
Known
Air Infiltration Rate Method
must be used. If the
building in which this appliance is to be installed
is unusually tight, PB Heat recommends that the
air infiltration rate be determined.
b.
Known Air Infiltration Rate Method:
Where
the air infiltration rate of a structure is known,
the minimum required volume of indoor air for
appliances other than fan assisted and for the
Series GM™ Boiler shall be determined as follows:
where:
Iother
= Input of appliances other than fan
assisted in Btu/hr
ACH = air change per hour (percent of the
volume of the space exchanged per
hour, expressed as a decimal)
For fan assisted appliances, calculate the required
volume of air using the following equation:
Ifan
= Input of the fan assisted appliances in
Btu/hr
Note: These calculations are not to be used for
infiltration rates greater than 0.60 ACH.
3. Indoor Air Opening Size and Location: Openings
connecting indoor spaces shall be sized and located
as follows:
a.
Combining spaces on the same floor:
Provide two permanent openings communicating
with additional spaces that have a minimum free
area of 1 in² per 1000 Btu/hr (22 cm² per 1000 W)
of the total input rating of all gas fired equipment
but not less than 100 in² (645 cm²). One opening
is to begin within 12 inches (305 mm) of the
top of the space and the other is to begin within
12 inches (305 mm) of the floor. The minimum
dimension of either of these openings shall be 3
inches (76 mm). See Figure 1.1 for an illustration
of this arrangement.
b.
Combining spaces on different floors:
Provide one or more permanent openings
communicating with additional spaces that have
a total minimum free area of 2 in² per 1000 Btu/
hr (44 cm² per 1000 W) of total input rating of
all equipment. See Figure 1.2 for an illustration
of this arrangement.
4. Outdoor Combustion Air: Outdoor combustion air
is to be provided through one or two permanent
openings. The minimum dimension of these air
openings is 3 inches (76 mm).
a.
Two Permanent Opening Method:
Provide
two permanent openings. One opening is to
begin within 12 inches (305 mm) of the top of
the space and the other is to begin within 12
inches (305 mm) of the floor. The openings are
to communicate directly or by ducts with the
outdoors or with spaces that freely communicate
with the outdoors. The size of the openings shall
be determined as follows:
PREINSTALLATION
Figure 1.1: Air Openings – All Air from Indoors
on the Same Floor
Figure 1.2: Air Openings – All Air from Indoors
on Different Floors
21 ft
3
I
other
ACH
1000
Btu
/
hr
Required Volume
other
=
(
)
15 ft
3
I
fan
ACH
1000
Btu
/
hr
Required Volume
fan
=
(
)
Summary of Contents for Peerless Boilers GM Series
Page 1: ...GM Boilers Series Gas Installation Operation Maintenance Manual...
Page 21: ...19 ELECTRICAL Figure 6 2 Wiring Diagram Spark Ignited Pilot Hydrolevel 3200 Limit control...
Page 25: ...23 Figure 8 3 Operating Instructions Spark Intermittent Ignition START UP PROCEDURES...
Page 26: ...24 START UP PROCEDURES Figure 8 4 Operating Instructions Spark Intermittent Ignition...
Page 38: ...REPAIR PARTS Figure 12 3a Figure 12 3b 36...
Page 40: ...REPAIR PARTS 13 14 15 16 17 24 25 22 21 20 19 18 23 Figure 12 4 38...
Page 42: ...NOTES 40...