26
Burner inputs in Btu/hr for various meter timings and
heat values. (Table based on 2 cubic feet of gas through
meter).
(Metric) Burner inputs in Watts for various meter timings
and heat values. (Table based on .05 cubic meters of
gas through meter).
E. CHECK-OUT PROCEDURE
1. After starting the boiler, be certain all controls are
working properly. Check to be sure that the limit will
shut off the boiler in the event of excessive water
temperature. This can be done by lowering the limit
setting until the main burners shut down. When
proper limit function is confirmed, return the dial to
its previous setting.
2. Intermittent Ignition System—To check operation of
the ignition system safety shut-off features:
a. Refer to Figure 8.3 Operating Instructions for
placing the boiler in operation and Section
6, paragraph B, Intermittent Ignition System
Operating Sequence.
b. Observe boiler operation through one complete
cycle.
3. Low Water Cut-Off – Consult the manufacturer’s
instructions for the low water cut-off operational
check procedure. Note that low water cut-off feature
is incorporated in the Hydrolevel 3200 Control with
standard Electro-Well.
4. Check the system to make sure there are no leaks
or overfilling problems which might cause excessive
make-up water to be added. Make-up water causes
liming in the boiler and brings in oxygen. Oxygen
can cause severe damage to the boiler though
oxygen corrosion pitting.
5. Check the expansion tank and automatic fill valve (if
used) to confirm that they are operating correctly. If
either of these components causes high pressure in
the system, the boiler relief valve will weep or open,
allowing fresh water to enter the system.
6. Do not allow the system controls to subject the boiler
to excessively low water temperatures, which would
cause condensation of flue gases and corrosion of
the boiler. Operate the boiler at a temperature above
130°F (54°C). Adjust the boiler limit as required to
maintain boiler temperature above this level.
7. Check the general condition of the system including
piping support, joints, etc. Check cleanliness of the
radiators, baseboard units and/or convectors. Clean
them to the extent possible. If radiators do not heat
evenly, vent any remaining air from them.
8. Review operation and User’s Information Manual
with end-user.
9. Complete the Warranty Card and submit it to PB
Heat.
10. Hang the Installation, Operation and Maintenance
Manual and User’s Information Manual in an
accessible position near the boiler.
START-UP PROCEDURES
Table 8.1a:
Meter Conversion – Natural Gas
Table 8.1b: Meter Conversion – Natural Gas
Time that
meter is
read (sec)
Heat Value of Gas
(Btu/cubic foot)
1,000
1,025
1,050
15
480,000
492,000
504,000
20
360,000
369,000
378,000
25
288,000
295,200
302,400
30
240,000
246,000
252,000
35
205,714
210,857
216,000
Time that
meter is
read (sec)
Heat Value of Gas
(kJ/cubic meter)
37,300
38,200
39,100
15
124,333
127,333
130,333
20
93,250
95,500
97,750
25
74,600
76,400
78,200
30
62,167
63,667
65,167
35
53,286
54,571
55,857
Summary of Contents for Peerless Boilers GM Series
Page 1: ...GM Boilers Series Gas Installation Operation Maintenance Manual...
Page 21: ...19 ELECTRICAL Figure 6 2 Wiring Diagram Spark Ignited Pilot Hydrolevel 3200 Limit control...
Page 25: ...23 Figure 8 3 Operating Instructions Spark Intermittent Ignition START UP PROCEDURES...
Page 26: ...24 START UP PROCEDURES Figure 8 4 Operating Instructions Spark Intermittent Ignition...
Page 38: ...REPAIR PARTS Figure 12 3a Figure 12 3b 36...
Page 40: ...REPAIR PARTS 13 14 15 16 17 24 25 22 21 20 19 18 23 Figure 12 4 38...
Page 42: ...NOTES 40...