12
A. DRAFT HOOD
1. The boiler is equipped with a draft hood designed
to:
a. provide for the ready escape of flue gases from
the boiler in the event of no draft.
b. prevent a backdraft from entering the boiler.
c. control stack draft during operation.
The draft hood must be installed without alteration.
Make certain there are no obstructions to airflow to
the relief opening.
2. Position draft hood with 1” (25 mm) diameter hole
in conical portion of draft hood (for vent safety
shutoff switch) towards front right corner of boiler.
Secure to flue collector with sheet metal screws. See
Figure 4.1.
B. BLOCKED VENT SWITCH
Attach blocked vent switch assembly to draft hood as
shown in Figure 4.1. GM-e-05/06 assembly includes
a factory installed adapter plate to connect the 5/8”
diameter switch to the 1” diameter hole in the draft
hood. To adjust harness length, squeeze strain relief
bushing to release from jacket. Remove excessive slack
in harness.
4. VENTING
VENTING
Figure 4.2: Venting Multiple Appliances
SHEET METAL
SCREWS
BLOCKED VENT
SWITCH ASSEMBLY
BLOCKED VENT
SWITCH WIRING
HARNESS
Figure 4.1: Draft Hood and Vent Safety Shutoff
Switch Installation
Summary of Contents for Peerless Boilers GM Series
Page 1: ...GM Boilers Series Gas Installation Operation Maintenance Manual...
Page 21: ...19 ELECTRICAL Figure 6 2 Wiring Diagram Spark Ignited Pilot Hydrolevel 3200 Limit control...
Page 25: ...23 Figure 8 3 Operating Instructions Spark Intermittent Ignition START UP PROCEDURES...
Page 26: ...24 START UP PROCEDURES Figure 8 4 Operating Instructions Spark Intermittent Ignition...
Page 38: ...REPAIR PARTS Figure 12 3a Figure 12 3b 36...
Page 40: ...REPAIR PARTS 13 14 15 16 17 24 25 22 21 20 19 18 23 Figure 12 4 38...
Page 42: ...NOTES 40...