Paul thermos 300 DC Operating Instructions Manual Download Page 8

Status 14.07.09 

 
We reserve the right to make 
changes favouring technical 
progress.

 

Operating Instructions 

thermos 200 / 300 DC 

with automatic control unit

 

®

WÄRMERÜCKGEWINNUNG

 

© Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland  

Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55  • E-Mail: [email protected] • Internet: www.paul-lueftung.de 

 

4

The control unit of the MVHR must be equipped for controlling a frost protection heater. The frost 
protection heater has to be activated and parameterised via the control unit in the system setup menu (see 
User Guidance of Automatic Control Unit, Section 2.1). 

 
2.5 

Electric duct heater

 

 

Electric or ISO duct heaters can be used as back-up heaters for the supply air. They are controlled via the 
MVHR control system specifically equipped for this purpose. The duct heaters include the prescribed 
safety appliances. A duct temperature sensor is used to limit the air temperature to 50°C, because higher 
temperatures would cause dust particles to smoulder (undesired smells). The duct heaters are switched on 
or off as a function of room temperature, duct temperature and temperature setpoint. 
If the room temperature falls below the setpoint, the duct heater will start operating, and will stop when the 
setpoint is exceeded. The room temperature is recorded by a temperature sensor in the programmer or by 
an external room temperature sensor. 
The setpoint is selected and the heater activated via the control unit (see User Guidance of Automatic 
Control Unit, Section 2.4). A lower night-time temperature can be programmed. Connections shall be made 
according to Appendix 2.1, Appendix 3.2, and Appendix 4.4.a for electric back-up duct heaters with ohmic 
heating element, and to Appendix 4.4.b for ISO back-up duct heaters with PTC heating element. 

 

Note:

  The control unit can operate only 

one

 heating circuit (electric duct heater, hot water duct heater, or 

heating circuit)! 

 
2.6 

Hot water duct heater

 

 

A hot water duct heater can be used to heat the supply air. It is controlled via the MVHR control system 
specifically equipped for this purpose. A duct temperature sensor is used to limit the air temperature to 50 
°C, because higher temperatures would cause dust particles to smoulder. The duct heater is switched on 
or off (hot water circulating pump) as a function of room temperature, duct temperature and temperature 
setpoint. 
If the room temperature falls below the setpoint, the duct heater will start operating, and will stop when the 
setpoint is exceeded. The room temperature is recorded by a temperature sensor in the programmer or by 
an external room temperature sensor. 
The setpoint is selected and the heater activated via the control unit (see User Guidance of Automatic 
Control Unit, Section 2.4). A lower night-time temperature can be programmed. Connections shall comply 
with Appendix 2.1, Appendix 3.2, and Appendix 4.2. 

 

Note:

  The control unit can operate only 

one

 heating circuit (hot water duct heater, electric duct heater, or 

heating circuit)! 

 

2.7 

Control for 1 heating circuit 

(e. g. circulating pump for panel heaters or radiators) 

 

The control unit of the MVHR must be specifically equipped for this purpose. A temperature sensor is used 
to limit e.g. the flow temperature to 50°C (parameterisable). The heating circuit is switched on or off as a 
function of room temperature, flow temperature and temperature setpoint. 
If the room temperature falls below the setpoint, the heating circuit (pump) will start operating, and will stop 
when the setpoint is exceeded. The room temperature is recorded by a temperature sensor in the 
programmer or by an external room temperature sensor. 
The setpoint is selected and the heating circuit activated via the control unit (see User Guidance of 
Automatic Control Unit). A lower night-time temperature can be programmed. The connection shall be 
made according to Appendix 4.2 as described for the hot water heating register. 

 

Note:

 The control unit can operate only 

one

 heating circuit (heating circuit, hot water duct heater, or 

electric duct heater)! 

 

2.8 

External boost switch

 

 

One or several boost switches can be connected with the programmer. Pressing the boost switch means 
maximum fan power for 15 minutes. The connection shall be made according to Appendix 4.1. 

 

Summary of Contents for thermos 300 DC

Page 1: ...uctions P lease keep next to the MVHR unit P lease keep next to the MVHR unit W RMER CKGEWINNUNG with automatic control unit Components suitable for Passive House Dr Wolfgang Feist Status 07 09 Paul W...

Page 2: ......

Page 3: ...sensor Additional programmer MVHR Installation Installation of the mechanical ventilation heat recovery MVHR unit air duct connections Power supply electric control Connection and maintenance of the c...

Page 4: ...endix 1 1 Terminal assignment of control unit Appendix 1 2 Internal terminal diagram thermos 200 300 DC Appendix 2 1 External connection diagram thermos 200 300 DC Appendix 2 2 Legend of external conn...

Page 5: ...ustomer who shall also provide the control unit s connection with the power supply 1 2 Housing heat and sound insulation The fan and heat exchanger box subassemblies are releasably connected by means...

Page 6: ...ck and the programmer with display and room temperature sensor The control system with the programmer controls enables the user to freely select the minimum normal and maximum ventilation steps withou...

Page 7: ...ogue flow sensors to be integrated in straight tubes of the same diameter see Appendix 3 3 and Appendix 4 5 When setting the parameters it is possible to store a flow disbalance The constant flow cont...

Page 8: ...d via the MVHR control system specifically equipped for this purpose A duct temperature sensor is used to limit the air temperature to 50 C because higher temperatures would cause dust particles to sm...

Page 9: ...icone to create airtight connections After each cleaning operation every 2 years re assemble the fan box and the heat exchanger box press tightly and lock them using the blue assembly caps Leave enoug...

Page 10: ...ped at their low point refer to Figure 2 Schematic sketch for condensate discharge line with MVHR 90 thermos Figure 1 Caution U bend traps can dry out Always refill water when starting up the unit hea...

Page 11: ...the duct install a throttle valve or a foam flow restrictor Balance the air flows at the MVHR unit if required Equal supply and extract flows vary the fan power to balance the flows the extract flow m...

Page 12: ...the front 10 Re connect the MVHR unit with the power supply re energise General inspection of the MVHR unit 1 Contamination 2 Electrical safety 3 Leaktightness of condensate connection The supply and...

Page 13: ...Mail info paul lueftung de Internet www paul lueftung de 1 1 Menu structure and logical links A graphical display of 128 x 64 pixels is provided for the menu dialogue There are 2 buttons on the right...

Page 14: ...or code is indicated refer to error code table Pressing the button TA2 illuminates the display screen for 1 minute Operating a boost switch connected to the programmer causes the ventilation to run at...

Page 15: ...nd TA5 up down arrows press TA2 to select an item Press TA1 to return to the basic menu The pre selected function is System Off 1 2 1 Menu Settings 0 System Off The control system is switched off none...

Page 16: ...controlled Electric duct heater ohmic heating element is controlled ISO duct heater PTC heating element is controlled Static heating elements pump is controlled Night reduction Reduction of room temp...

Page 17: ...0 days Press TA3 and TA4 to increase or reduce the number of days for the interval After reset the day counter starts a countdown for the remaining service time After the interval has lapsed the basic...

Page 18: ...days but to assign Program 2 to the weekend The programs can be edited by the user in the menu Programs 5 0 Use TA5 to scroll through the weekdays and press TA3 TA4 to select the desired program numb...

Page 19: ...rmal Normal ventilation max Maximum ventilation A system is generally designed and dimensioned for normal ventilation So the minimum or zero steps mean that there is less air exchange than assumed in...

Page 20: ...rams will not run properly Press TA5 to scroll through the time and date until all values are set then press Save to acknowledge and store the values Save will appear on the screen when all settings h...

Page 21: ...turn to the Menu Settings T intake Intake air temperature at the inlet of the unit T supply Supply air temperature at the outlet of the unit T heat Supply air temperature at the outlet of the duct hea...

Page 22: ...s always programmed for the highest configuration whether or not your specific system can use and evaluate all options mentioned here System setup 9 0 9 Enable TA1 0 Frost prot heater 1 Bypass su wi 2...

Page 23: ...pass su wi Bypass su wi 9 1 0 TA1 0 Temperatures 1 Servomotor ok TA2 TA5 TA4 TA3 Press TA5 to select a menu item and confirm with TA2 2 2 1 Menu System setup Temperatures Bypass su wi Bypass su wi 9 1...

Page 24: ...motor Bypass su wi Setup bypass su wi 9 1 1 0 TA1 min max act Bp1 100 255 100 TA2 NOTE The values are just examples TA5 TA4 TA3 Press TA5 to select a value and TA3 TA4 to adjust it min Closed max Open...

Page 25: ...ure below setpoint and Maximum duct temperature not reached DCTH Off Room temperature exceeds setpoint or Maximum duct temperature reached Example x0 21 0 C Duct heater ON T5 20 5 C H0 0 5 K Duct heat...

Page 26: ...needed in the system SUP EXT for positive fan adjustment e g ebm fans of series campus thermos atmos for negative fan adjustment e g Papst fans of series multi climos are used to adjust the response o...

Page 27: ...will restart automatically after validation with TA5 2 7 Menu System setup Enable 9 9 0 Enable 9 9 0 0 Frost prot heater ON TA1 1 PTC heater OFF 2 Brine ground HX OFF 3 Bypass 1 OFF ok TA2 4 Bypass 2...

Page 28: ...display shows x The button TA5 gives access to service menu 1 3 2 Service menu 1 Frost prot brine GHX valve Service1 FP brine GHX FHL Off T7 x TA1 x1 02 0 H1 01 0 STB FZ1 IFZ1 Brine GHX f Off T2 22 0...

Page 29: ...selected k cooling mode disabled heating is not possible T0 Room temperature X0 Room temperature setpoint H0 Hysteresis f r x0 x0 H0 T5 Duct temperature X5 Max duct temperature H5 hysteresis for x5 x...

Page 30: ...X X 0 30 X X X X X X X 0 45 X X X X X X X 1 00 X X X X X X X 1 15 X X X X X X X 1 30 X X X X X X X 1 45 X X X X X X X 2 00 X X X X X X X 2 15 X X X X X X X 2 30 X X X X X X X 2 45 X X X X X X X 3 00 X...

Page 31: ...X X X X 14 00 X X X X X X 14 15 X X X X X X 14 30 X X X X X X 14 45 X X X X X X 15 00 X X X X X X 15 15 X X X X X X 15 30 X X X X X X 16 00 X X X X X X 16 15 X X X X X X 16 30 X X X X X X 16 45 X X X...

Page 32: ...ngs 1 Settings 2 Settings 3 Settings 4 Unit in standby Enable ON OFF Filter change Temperature setpoints Programs day Unit OFF Air heating 1 0 Filter interval 2 0 Temperatures 3 0 Programs day 4 0 Nig...

Page 33: ...4 0 Unit OFF Tempe ratures 9 1 0 0 HP bypasses 9 3 0 0 Cut off temperature Servo motor 9 1 1 0 Fixing temp window for flap valve Position OFF 9 3 1 0 Define solar pump Position Heat 9 3 2 0 Position C...

Page 34: ...1 0XXXXXXXXX No faults in this group 1XXXXXXXXX FAULT IN ROOM TEMPERATURE SENSOR T0 2XXXXXXXXX FAULT IN INTAKE AIR TEMPERATURE SENSOR T1 3XXXXXXXXX FAULT IN ROOM TEMPERATURE SENSOR T0 FAULT IN INTAKE...

Page 35: ...X No faults in this group X1XXXXXXXX FAULT IN EXTRACT AIR TEMPERATURE SENSOR T4 X2XXXXXXXX FAULT IN BACK UP HEATER DUCT TEMPERATURE SENSOR T5 X3XXXXXXXX FAULT IN EXTRACT AIR TEMPERATURE SENSOR T4 FAUL...

Page 36: ...T FZ4 FAULT IFZ1 FAULT IFZ4 XXXFXXXXXX FAULT FZ1 FAULT FZ4 FAULT IFZ1 FAULT IFZ4 XXXX0XXXXX No faults in this group XXXX1XXXXX FAULT FROST PROTECTION HEATER IS NOT DETECTED XXXX2XXXXX FAULT BACK UP DU...

Page 37: ...tion of the control system it is possible to set up simple as well as complex control configurations covering all PAUL mechanical ventilation control variants The photograph shows a fully equipped con...

Page 38: ...ine pump on PP 8 GND 9 NPN open collector output PP power standby from HCE 10 GND 11 PWM Out fan2 extract air 12 GND 13 PWM Out fan1 supply air 14 GND 15 24P from PP 16 GND 17 24P from PP 18 GND 19 24...

Page 39: ...rotection pre heater additional switch module required Air duct heater additional switch module required Constant flow control Connector pin assignment Plug X3 1 T1 NTC temp sensor for intake air at i...

Page 40: ...echnical Description Automatic Control thermos 200 300 DC Paul W rmer ckgewinnung GmbH August Horch Stra e 7 08141 Reinsdorf Deutschland Tel 49 0 375 303505 0 Fax 49 0 375 303505 55 E Mail info paul l...

Page 41: ...tallation in building system refer to electrical connection instructions Fuses single phase mains 1x16 A external three phase mains 3x16 A external internal mains fuse 2A M internal on PP internal fus...

Page 42: ...ion of the power pack take care to ensure the individual phases are loaded symmetrically Use a 3 core cable for direct load connection to connector 2 of the power module inverted 3 pole plug To select...

Page 43: ...utschland Tel 49 0 375 303505 0 Fax 49 0 375 303505 55 E Mail info paul lueftung de Internet www paul lueftung de 7 4 1 Terminal connection plan for switch module Switch module 2 1 KW 230 V INPUT from...

Page 44: ...cation The programmer can be used to view enter or change any parameters of the mechanical ventilation control unit The programmer offers menu dialogues so all settings are self explaining There are t...

Page 45: ...lve frost protection brine pump T2 Outdoor temperature x2 min temp GHX valve OPEN pump ON x4 max temp GHX valve OPEN pump ON H2 hysteresis for x2 and x4 x4 Menu 9 2 0 Setup GHX valve brine pump Valve...

Page 46: ......

Page 47: ......

Page 48: ......

Page 49: ...is switched on and off by the control unit Sensor equipment for electric back up duct heater Comprising flow indicator thermal cut out and duct temperature sensor for monitoring the electric duct hea...

Page 50: ...ion appropriate length to be laid by customer l Sensor line T5 control unit Copper strand with PVC insulation LiYY 2 0 5mm 5V DC Sensor mit Kabel und Stecker werksseitig vorkonfektioniert nur Sensor w...

Page 51: ...xt to each other or in the same cable duct because this might cause parasitic induction and disturb the sensor elements A minimum distance of 20 cm 8 inches is recommended Install the control unit in...

Page 52: ......

Page 53: ......

Page 54: ......

Page 55: ......

Page 56: ......

Page 57: ......

Page 58: ......

Page 59: ......

Page 60: ......

Page 61: ......

Page 62: ......

Page 63: ......

Page 64: ......

Page 65: ......

Page 66: ......

Page 67: ...n single phase 230V 50Hz three phase 3 x 230V 50 Hz with frost protection and back up duct heater options Central control unit LxWxD mm 340x300x80 or 340x300x140 with frost protection and back up duct...

Page 68: ...ower input below 2 W manual adjustment of ventilation steps off minimum normal maximum programmer can be installed in any place in the house ventilation steps programmable in 1 increments 30 100 of ma...

Page 69: ...e filters in fresh air pipe Suctioning in of outside air also in the soil heat exchanger Quarterly Year I II III IV 200 201 201 201 201 4 Exhaust hood Clean grease filters every 6 8 weeks with hot wat...

Page 70: ...d heat exchanger c at extract air valves d check filter change intervals by inspecting the records of the tenant owner e record any filter change in writing 3 Check intake air ducts for contamination...

Page 71: ...3 Check insulation visual examination a damage b moisture penetration c connection point at MVHR unit d line to valve connection 14 Check fire dampers if any a inspect test report b latch and trigger...

Page 72: ...s Very dirty Fan speed ratio clean extract supply air Supply air Ventilation step Project Data Measurement data Valve No Room description m h m s m h m s mm Extract air Ventilation step Project Data M...

Reviews: