3.3
Service menu 2 Back-up duct heaters
-----------------------
|Service2 Backup DCTH |
|FHLK Off | TA1
|T0:22.0° x0:01.0° |
|H0:01.0° T5:30.0° |
|x5:50.0° H5:01.0° |
|STB4:+ FZ4:+ IFZ4:+ | TA2
| |
| -> |
-----------------------
TA5 TA4 TA3
This menu shows the parameters of the back-up duct heater.
FHLK capital letters mean:
small letters mean:
F duct heater enabled
f duct heater not enabled
H hardware detected
h hardware not detected
L ventilation enabled
l ventilation not enabled
K cooling mode selected
k cooling mode disabled
(heating is not possible)
T0 Room temperature
X0 Room temperature setpoint
H0 Hysteresis für x0 (x0 +/- H0)
T5
Duct temperature
X5
Max. duct temperature
H5 hysteresis for x5 (x5 +/- H5)
3.4
Service menu 3 Summer/winter bypass
-----------------------
|Service3 Bp_su_wi |
|FONKW | TA1
|T1:02.0° min:100 |
|T4:02.0° max:255 |
|x41:24.0° act:100 |
|x42:18.0 | TA2
|H4:01.0 |
| -> |
-----------------------
TA5 TA4 TA3
This menu shows the parameters for the summer/winter bypass.
FONKW
capital letters mean:
small letters mean:
F bypass enabled
f bypass not enabled
O bypass in proper position
o bypass in wrong position
N back-up heater enabled
n back-up heater disabled
K cooling mode enabled
k cooling mode disabled
W heat pump ON
w heat pump OFF
T1
Intake air temperature at the inlet of the unit
T4
Extract air temperature
min:
Valve position CLOSED
max:
Valve position OPEN
act:
actual valve position
X41
selected temperature for bypass OPEN
X42
selected temperature for bypass CLOSED
H4
hysteresis for x41/x42 (x +/- H4)
Summary of Contents for thermos 300 DC
Page 2: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......