The recommended maximum distance of the horizontal link (home run and
patch cables) should not exceed 325 feet: 295 for the home run and 30 feet
split between the ends of the home run cable.
Do not put sharp bends into individual wire pairs when terminating.
Cables that have been bent or kinked beyond the acceptable bend radius
cannot be straightened to correct a problem. Cables should not be bent tighter
than ½ inch radius, or about the size of a quarter.
Untwisting of pairs when making a termination should not exceed ½ inch.
Limit the amount of cable insulation stripped to protect the pairs from
untwisting or separating.
Limit the amount of twisting on the cable. Excessive twisting can cause the
separation of the individual pairs.
Use an adequate amount of hangers when suspending Cat5e cables to avoid
cable stress.